struction mode operation, 365-day real time clock with 7 
day programming plus holiday scheduling is built-in. Two 
different modes of demand ventilation are achieved 
through the INTELLI-Comfort™ using CO
2
 sensors. It 
uses an inside CO
2
 sensor to perform Demand Ventila-
tion. It can also use an Outside CO
2
 sensor to perform Dif-
ferential Demand Ventilation. It uses a Patented Comfort 
Ventilation algorithm to provide comfortable ventilation air 
temperature. The patented economizer-loading algorithm 
will protect the equipment when harsh operating condi-
tions exist. Humidity in the occupied space or return duct 
can be monitored and controlled via humidity sensors and 
the on-board connection for hot gas re-heat system. It 
uses the INTELLI-Start™ algorithm to maximize energy 
savings by recovering the building from the Unoccupied 
Setpoints to the Occupied Setpoints just in time for the 
Occupied Time Period to begin. The Simplicity® INTELLI-
Comfort™ balances space temperature, ventilation air 
temperature, CO
2
 and humidity for ultimate comfort.
Simplicity® INTELLI-Comfort™ with ModLINC CON-
TROL - 
The York® Simplicity® INTELLI-Comfort™ with 
ModLINC control is factory installed. It includes all the fea-
tures of the INTELLI-Comfort™ control with an additional 
control to translate communications from MODBUS to the 
BACnet MSTP protocol.
Novar® BAS CONTROL - The Novar® ETC-3 building 
automation system controller is factory installed. Includes 
supply air sensor, return air sensor, dirty filter indicator 
switch, and air proving switch.
JOHNSON CONTROLS BAS CONTROL - The Johnson 
Control YK-UNT-1126 building automation system control-
ler is factory installed. Includes supply air sensor, return 
air sensor, dirty filter indicator switch, and air proving 
switch.
CPC BAS CONTROL - The Computer Process Controls 
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes sup-
ply air sensor, return air sensor, dirty filter indicator switch 
and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell W7750C 
building automation system controller is factory installed. 
Includes air supply sensor, return air sensor, dirty filter 
indicator switch, and air proving switch.
• COIL GUARD - Customers can purchase a coil guard kit 
to protect the condenser coil from damage. This is not a 
hail guard kit.
• SMOKE DETECTORS - (supply air & return air) The 
smoke detectors stop operation of the unit by interrupting 
power to the control board if smoke is detected within the 
air compartment.
• STAINLESS STEEL HEAT EXCHANGER - For 
applications in corrosive environments, this option 
provides a full stainless steel heat exchanger assembly.
• STAINLESS STEEL DRAIN PAN - An optional rust-proof 
stainless steel drain pan is available to provide years of 
trouble-free operation in corrosive environments.
• PHASE MONITORS - Designed to prevent unit damage. 
The phase monitor will shut the unit down in an out-of-
phase condition.
• HIGH SPEED DRIVE - May include a belt, blower pulley, 
motor pulley or a motor change to enhance blower 
performance.
• DIRTY FILTER SWITCH - This kit includes a differential 
pressure switch that energizes the fault light on the unit 
thermostat, indicating that there is an abnormally high 
pressure drop across the filters. Factory installed option or 
field installed accessory.
• HINGED FILTER DOOR/”TOOLLESS” BLOWER AND 
ACCESS PANELS (not hinged) - This option allows for 
easy access and maintenance.
NOTE: Knobs are shipped separately within the unit to
prevent shipping damage. These must be field
installed for toolless operation.
• LOW SPEED DRIVE - Includes a motor change when 
high airflow is not required. (WR300 & WR240 only)
FIELD-INSTALLED ACCESSORIES
• SINGLE INPUT ELECTRONIC ENTHALPY 
ECONOMIZERS - Includes a slide-in / plug-in damper 
assembly with fully modulating spring-return motor 
actuator capable of introducing up to 100% outdoor air 
with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors 
the outdoor air and determines when the air is cool 
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must 
be field-assembled before installing.
• MOTORIZED OUTDOOR AIR INTAKE DAMPER - 
Includes a slide-in / plug-in damper assembly with a 2-
position, spring return motor actuator which opens to 
some pre-set position whenever the supply air blower is 
operating and will drive fully closed when the blower unit 
shuts down.
The rain hood is painted to match the basic unit and must 
be field-assembled before installing.
Factory installed smoke detectors in the return air, 
may be subjected to freezing temperatures during 
“off” times due to out side air infiltration. these smoke 
detectors have an operational limit of 32°F to 131°F. 
smoke detectors installed in areas that could be out 
side those limitations will have to be moved to prevent 
having false alarms.