York DF 072 User Manual

Page of 24
254599-YTG-C-0807
22
Unitary Products Group
insulated with a minimum 1/2” thick insulation, coated on the 
airside. Aluminum foil faced insulation shall be used in the 
furnace compartment and be fastened with ridged fasteners 
to prevent insulation from entering the air stream. Cabinet 
panels shall be “large” size, easily removable for servicing 
and maintenance. Full perimeter base rails shall be provided 
to assure reliable transit of equipment, overhead rigging and 
proper sealing on roof curb applications. Disposable 1" filters 
shall be furnished and be accessible through a removable 
access door, sealed airtight. Units filter track shall be 
designed to accommodate either 1” or 2” filters. Fan 
performance measuring ports shall be provided on the 
outside of the cabinet to allow accurate air measurements of 
evaporator fan performance without removing panels or 
creating air by-pass of the coils. Condensate pan shall be 
internally sloped and conform to ASHRAE 62-89 self-draining 
standards. Condensate connection shall be a minimum of 3/
4” I.D. female and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory 
installed belt drive assembly that includes an adjustable pitch 
motor pulley. Job site selected brake horsepower (B.H.P.) 
shall not exceed the motors nameplate horsepower rating, 
plus the service factor. Units shall be designed not to operate 
above service factor. Fan wheel shall be double-inlet type 
with forward-curved blades, dynamically balanced to operate 
smoothly throughout the entire range of operation. Airflow 
design shall be constant air volume. Bearings shall be sealed 
and permanently lubricated for longer life and no mainte-
nance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type, 
discharge air vertically, have aluminum blades riveted to a 
corrosion resistant steel spider bracket and shall be dynami-
cally balanced for smooth operation. The outdoor fan motor 
shall be totally enclosed with permanently lubricated bear-
ings, internally protected against overload conditions and 
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.
Shall be  internally protected with internal high-pres-
sure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muf-
fling to minimize vibration and noise, and be exter-
nally isolated on a dedicated, independent 
mounting.
Coils:
a.
Evaporator and condenser coils shall have alumi-
num plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.
Evaporator and Condenser coils shall be of the 
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall 
include:
a.
Thermal expansion devices (TXV’s). 
• DF072 uses a fixed orifice distributor.
b.
Filter drier/strainer to eliminate any moisture or for-
eign matter.
c.
Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary 
servicing or troubleshooting without losing charge.
d.
The refrigeration system shall provide at least 15°F 
of sub-cooling at design conditions.
UNIT CONTROLS
a.
Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or 
base unit, should any of the following standard 
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil. 
f.
If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor 
over temperature, over current protection.
h.
Unit shall operate with conventional thermostat 
designs and have a low voltage terminal strip for 
easy hook-up.
i.
Unit control board shall have on-board diagnostics 
and fault code display.
j.
Standard controls shall include anti-short cycle and 
low voltage protection, and permit cooling operation 
down to 0°F.
k.
Control board shall monitor each refrigerant safety 
switch independently.
l.
Control board shall retain last 5 fault codes in non 
volatile memory, which will not be lost in the event of 
a power loss.
GAS HEATING SECTION (SINGLE OR 2 STAGE)
Shall be designed with induced draft combustion with post 
purge logic, energy saving direct spark ignition, and redun-
dant main gas valve. Venter wheel shall be constructed of 
stainless steel for corrosion resistance. The heat exchanger 
shall be of the tubular type, constructed of T1-40 aluminized