York D1NA018 User Manual

Page of 21
035-18265-001-A-0202
Unitary Products Group
7
FIG. 4 - CENTER OF GRAVITY
49
1
8
25
24
47
1
4
CENTER OF GRAVITY
FRONT
OF
UNIT
CORNER “C”
CORNER “D”
CORNER “A”
CORNER “B”
TABLE 7 - UNIT WEIGHTS
MODEL
DNA
UNIT
SHIPPING
WEIGHT
(lbs.)
UNIT
OPERATING
WEIGHT
(lbs.)
CORNER OPERATING WEIGHTS
(lbs., location, see Figure 4)
“A”
“B”
“C”
“D”
018
365
360
91
88
89
92
024
365
360
91
88
89
92
030
395
390
98
95
96
99
036
400
395
100
96
98
101
042
405
410
104
100
101
105
048
475
470
119
115
116
120
060
480
475
120
116
117
122
TABLE 8 - ELECTRICAL DATA
MODEL
DNA
POWER SUP-
PLY
VOLTAGE
LIMITATIONS
1
COMPRESSOR
COND.
FAN
MOTOR,
FLA
SUPPLY
AIR
BLOWER
MOTOR,
FLA
MINIMUM
CIRCUIT
AMPACITY
MAX.
FUSE
SIZE,
AMPS
2
MAX.
HACR
BREAKER
SIZE,
AMPS
UNIT
POWER
FACTOR
TRANSFORMER
SIZE (VA)
3
MIN.
MAX.
RLA
LRA
018
208/230-1-60
187
253
9.0
48.0
1.1
2.2
14.5
20
20
.96
40
024
208/230-1-60
187
253
11.5
60.0
1.1
2.2
17.7
25
25
.96
40
030
208/230-1-60
187
253
14.7
73.0
1.1
2.2
21.7
30
30
.96
40
036
208/230-1-60
187
253
17.3
94.0
1.1
3.5
26.2
35
35
.96
40
042
208/230-1-60
187
253
20.5
120.0
1.1
3.5
30.2
40
40
.96
40
048
208/230-1-60
187
253
24.4
140.0
1.3
7.0
38.8
50
50
.96
40
060
208/230-1-60
187
253
28.9
175.0
1.3
7.0
44.4
60
60
.96
40
036
208/230-3-60
187
253
10.9
78.0
1.1
3.5
18.2
25
25
.96
75
042
208/230-3-60
187
253
14.1
110.0
1.1
3.5
22.2
30
30
.96
75
048
208/230-3-60
187
253
14.1
105
1.3
7.0
25.9
35
35
.96
75
060
208/230-3-60
187
253
15.5
125
1.3
7.0
29.5
40
40
.96
75
036
460-3-60
414
504
5.8
40.0
0.6
1.8
9.6
15
15
.96
75
042
460-3-60
414
504
7.1
54.0
0.6
1.8
11.2
15
15
.96
75
048
460-3-60
414
504
7.1
55.0
0.7
3.5
13.1
20
20
.96
75
060
460-3-60
414
504
8.8
66.5
0.7
3.5
15.4
20
20
.96
75
036
575-3-60
518
630
4.5
32.0
0.4
1.5
7.5
15
15
.96
75
042
575-3-60
518
630
5.8
44.0
0.4
1.5
9.1
15
15
.96
75
048
575-3-60
518
630
5.7
45.0
0.6
2.8
10.5
15
15
.96
75
060
575-3-60
518
630
7.1
50.0
0.6
2.8
12.3
15
15
.96
75
Note; Electrical data based on 104°F outdoor air ambient temperature.
1
= Rated in accordance with ARI Standard 110, utilization range “A”.
2
= Dual element, time delay type.
3
= If economizer or motorized damper are to be used, 75 VA is required. Refer to price pages for future details.