TABLE 2: CAPACITY RATINGS IMPERIAL
Model
Cooling Capacity
Sound 
Rating
 (dB)
Nominal 
Electric
Heat 
Capacity
 (kW)
1
Gas Heat Capacity
(80 / 67-95°F)
Input
 (MBH)
Output
 (MBH)
Temp
Rise (°F)
Gas Line
Size
 (in. OD)
Cooling Cap. (MBH)
Options
MBH
EER
090
DM
89
9.00
87
7, 14,
18, 27
-
-
-
-
10
-
-
-
-
120
96
15-45
3/4
15
-
-
-
-
180
144
30-60
3/4
120
DM
116
9.0
85
14, 18,
27, 41
-
-
-
-
15
-
-
-
-
180
144
20-50
3/4
150
DM
138
9.0
84
14, 18,
27, 41
-
-
-
-
15
-
-
-
-
180
144
10-40
3/4
1. Electric heaters rated at 415V.  See tables 10 through 12 for kW ratings at 380V.
TABLE 3: CAPACITY RATINGS METRIC
Model
Cooling Capacity
Sound 
Rating
 (dB)
Nominal 
Electric
Heat 
Capacity
 (kW)
1
Gas Heat Capacity
Input
 (kW)
Output
 (kW)
Temp
Rise
(°C)
Gas Line
Size
(mm. OD)
(27/19-35°C)
Cooling Cap.
(kW)
Options
kW
CoP
2
090
(26.4)
DM
26.1
2.64
87
7, 14,
18, 27
-
-
-
10
-
-
-
-
35.1
28.1
8.3-25
19.05
15
-
-
-
-
52.7
42.2
17-33
19.05
120
(35.1)
DM
34.0
2.64
85
14, 18,
27, 41
-
-
-
-
15
-
-
-
-
52.7
42.2
11-28
19.05
150
(43.9)
DM
40.4
2.64
84
14, 18,
27, 41
-
-
-
-
15
-
-
-
-
52.7
42.2
5.6-22
19.05
1. Electric heaters rated at 415V.  See tables 10 through 12 for kW ratings at 380V
2. CoP = Co-efficient of Performance (CoP = Cooling Capacity (kW) / Power Input (kW))