York DM150 User Manual

Page of 36
036-21044-003-A-0304
Unitary Products
17
TABLE 7: COOLING CAPACITY 35.1 KW UNIT - METRIC
Air On
Evap. Coil
Temperature of Air on Condenser Coil 29°C
Temperature of Air on Condenser Coil 35°C
m
3
/s
WB
(°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
1.42
22
43
11.2
24
22
19
16
14
-
-
40
12.0
23
21
18
16
13
-
-
19
39
10.8
30
28
25
22
20
17
15
36
11.6
29
26
24
21
19
16
14
17
37
10.5
35
33
30
28
25
23
20
34
11.2
34
32
30
27
25
22
20
14
36
10.6
36
34
31
29
26
24
21
32
11.4
32
32
30
27
25
22
20
1.65
22
44
11.4
26
23
20
17
14
-
-
41
12.2
25
22
19
16
13
-
-
19
40
11.0
33
30
27
24
21
18
15
37
11.7
31
28
25
22
19
16
13
17
37
10.6
36
35
32
29
26
23
21
34
11.4
34
34
31
28
25
23
20
14
36
10.7
36
35
34
31
28
25
22
33
11.5
33
33
31
28
26
23
20
1.89
22
44
11.6
28
25
22
18
15
-
-
41
12.4
27
24
20
17
14
-
-
19
40
11.2
35
32
28
25
22
18
15
37
11.9
34
30
27
23
20
16
13
17
37
10.8
37
37
34
31
28
24
21
35
11.5
35
35
33
30
26
23
20
14
37
10.9
37
37
36
32
29
25
22
33
11.7
33
33
33
30
26
23
20
2.12
22
45
11.7
31
27
23
19
15
-
-
42
12.4
30
26
22
19
15
-
-
19
41
11.3
38
34
30
26
22
19
15
38
12.0
36
33
29
25
21
18
14
17
38
10.9
38
38
37
33
29
25
21
35
11.6
35
35
34
31
27
23
19
14
37
11.0
37
37
37
33
29
25
21
34
11.7
34
34
34
30
26
22
18
2.36
22
46
11.7
33
29
24
20
16
-
-
42
12.5
33
29
24
20
16
-
-
19
41
11.4
41
36
32
28
23
19
15
38
12.1
38
36
32
27
23
19
14
17
39
11.0
39
39
39
34
30
26
21
36
11.7
36
36
36
31
27
23
18
14
38
11.1
38
38
38
34
29
25
20
34
11.8
34
34
34
30
25
21
16
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
1.42
22
38
12.8
22
20
17
15
12
-
-
36
13.5
21
18
16
13
11
-
-
19
34
12.3
28
25
23
20
18
15
13
31
13.0
26
24
21
19
16
14
11
17
32
11.9
32
30
28
25
23
20
18
30
12.6
30
29
26
24
21
18
16
14
30
12.1
30
30
27
25
22
20
17
29
12.8
29
27
25
22
20
17
15
1.65
22
38
13.0
24
21
18
15
12
-
-
36
13.7
23
20
17
14
11
-
-
19
34
12.5
30
27
24
21
18
15
12
31
13.2
29
26
23
20
17
14
11
17
32
12.1
32
31
30
27
24
21
18
30
12.8
30
29
28
25
22
19
16
14
31
12.3
31
30
29
26
23
20
17
29
13.0
29
28
27
24
21
18
15
1.89
22
38
13.1
26
23
19
16
13
-
-
36
13.9
25
22
18
15
11
-
-
19
34
12.7
32
29
26
22
19
15
12
31
13.4
31
28
24
21
18
14
11
17
32
12.3
32
32
32
28
25
21
18
30
13.0
30
30
30
26
23
20
16
14
31
12.4
31
31
31
27
24
21
17
29
13.2
29
29
29
25
22
18
15
2.12
22
39
13.2
29
25
21
17
13
-
-
36
14.0
27
24
20
16
12
-
-
19
35
12.7
34
32
28
24
20
16
12
31
13.5
31
30
26
22
19
15
11
17
33
12.4
33
33
32
29
25
21
17
31
13.1
31
31
31
27
23
19
15
14
31
12.5
31
31
31
27
24
20
16
29
13.3
29
29
29
25
21
17
14
2.36
22
40
13.3
31
27
23
18
14
-
-
37
14.1
30
25
21
17
12
-
-
19
35
12.8
35
34
30
26
21
17
13
32
13.6
32
32
28
24
20
15
11
17
33
12.5
33
33
33
29
25
20
16
31
13.2
31
31
31
27
22
18
14
14
32
12.6
32
32
32
27
23
19
14
30
13.4
30
30
30
25
21
17
12
Temperature of Air on Condenser Coil 52°C
1.42
22
34
14.2
20
17
15
12
10
-
-
19
28
13.7
25
23
20
18
15
12
10
17
28
13.3
28
27
24
22
19
17
14
14
27
13.5
27
25
22
20
17
15
12
1.65
22
33
14.5
22
19
16
13
10
-
-
19
28
13.9
27
25
22
19
16
13
10
17
28
13.5
28
27
26
23
20
17
14
14
26
13.8
26
26
24
21
18
15
12
1.89
22
33
14.7
24
21
17
14
10
-
-
19
27
14.2
27
27
23
20
16
13
10
17
27
13.8
27
27
27
25
21
18
15
14
26
14.0
26
26
26
23
19
16
12
2.12
22
34
14.8
26
22
18
14
10
-
-
19
28
14.3
28
28
25
21
17
13
9
17
28
13.8
28
28
28
25
21
17
13
14
27
14.1
27
27
27
23
19
15
11
2.36
22
35
14.9
28
24
19
15
11
-
-
19
29
14.4
29
29
27
22
18
13
9
17
29
13.9
29
29
29
25
20
16
12
14
28
14.2
28
28
28
23
19
15
10
1 These capacities are gross ratings.  For net 
capacity, deduct air blower motor.  Refer to the 
appropriate Blower Performance Table for the 
kW of the supply air blower motor.
2 These ratings include condenser fan motors  
and the compressor motors but not the supply 
air blower motor.