Unitary Products
Balanced Heating – The Predator
®
 offers “Ultimate 
Heating Comfort” with a balance between 1
st
 and 2
nd
 
stage gas heating. The 1
st
 stage of a gas heat Predator
®
 
unit provides 60% of the heating capacity. Balanced 
heating allows the unit to better maintain desired temper-
atures.
Convertible Airflow Design – The side duct openings 
are covered when they leave the factory.  If a side sup-
ply/return is desired, the installer simply removes the two 
side duct covers from the outside of the unit and installs 
them over the down shot openings.  No panel cutting is 
required.  Convertible airflow design allows maximum 
field flexibility and minimum inventory.
System Protection - Suction line freezestats are sup-
plied on all units to protect against loss of charge and coil 
frosting when the economizer operates at low outdoor air 
temperatures while the compressors are running. Every 
unit has solid-core liquid line filter-driers and high and 
low-pressure switches. Internal compressor protection is 
standard on all compressors. Crankcase heaters are 
standard on reciprocating compressors. Scroll compres-
sors do not require crankcase heaters. Phase Monitors 
are standard on units with scroll compressors. This 
accessory monitors the incoming power to the unit and 
protects the unit from phase loss and reversed phase 
rotation.
Advanced Controls - 3FJMIF@FQV™ control boards have 
standardized a number of features previously available 
only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control 
allows all units to operate in the cooling mode down 
to 0°F (-17.8°C) outdoor ambient without additional 
assistance.  Optionally, the control board can be 
programmed to lockout the compressors when the 
outdoor air temperature is low or when free cooling 
is available.
Anti-Short Cycle Protection - To aid compressor 
life, an anti-short cycle delay is incorporated into the 
standard controls.  Compressor reliability is further 
ensured by programmable minimum run times.  For 
testing, the anti-short cycle delay can be temporarily 
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable.  Furthermore, the heating and cooling 
fan delay times are independent of one another.  All 
units are programmed with default values based 
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the 
high and low-pressure switches, the freezestats, the 
gas valve, if applicable, and the temperature limit 
switch on gas and electric heat units.  The unit con-
trol board will alarm on ignition failures, compressor 
lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent 
nuisance trouble calls, the control board uses a 
“three times, you’re out” philosophy.  The high and 
low-pressure switches and the freezestats must trip 
three times within two hours before the unit control 
board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a 
trouble light on the thermostat, if so equipped, and 
flash an alarm code on the control board LED.  Each 
high and low-pressure switch alarm as well as each 
freezestat alarm has its own flash code.  The control 
board saves the five most recent alarms in memory, 
and these alarms can be reviewed at any time. 
Alarms and programmed values are retained 
through the loss of power.
Reliable – From the beginning – All units undergo com-
puter automated testing before they leave the factory. 
Units are tested for refrigerant charge and pressure, unit 
amperage, and 100% functionality. For the long term – 
All Predator
®
 units are painted with a long lasting, pow-
der paint that stands up over the life of the unit. The paint 
used has been proven by a 750 hour salt spray test.
Flexible Placement – All models and configurations 
share the same cabinet/footprint and thus the same roof 
curb.  You have the flexibility to set one curb and choose 
the correct tonnage size and heating option after the 
internal loads have been determined.
To further simplify planning and installation, Predator
®
cabinets are designed to fit your roof. With the optional 
roof curb, the unit ductwork is designed to fit around 24” 
(610 mm) on-center joists or between 48” (1219 mm) on-
center joists.
The drain pan can be rotated to drain to either the front 
or the rear of the unit.  Additionally, the drain pan can be 
piped to drain through the roof curb.  As it is sometimes 
difficult to have a level installation, the drain pan features 
a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached 
base rails provide a solid foundation for the entire unit 
and protect the unit during shipment.  The rails offer fork-
lift access from 3 sides, and rigging holes are available 
so that an overhead crane can be used to place the units 
on a roof.
Easy Installation – Gas and electric utility knockouts are 
supplied in the unit underside as well as the side of the 
unit.  A clearly identified location is provided to mount a 
field supplied electrical disconnect switch.  Utility con-
nections can be made quickly and with a minimum 
amount of field labor.
All units are shipped with 2” (51 mm) filters installed.