York D2NA060 User Manual

Page of 21
2. Check for correct manifold gas pressures. See “Checking
Gas Input”.
3. Check the supply gas pressure. It must be within the limits
shown on rating nameplate. Supply pressure should be
checked with all gas appliances in the building at full fire. At
no time should the standby gas line pressure exceed 10.5",
nor the operating pressure drop below 4.5" for natural gas
units. If gas pressure is outside these limits, contact the lo-
cal gas utility for corrective action.
MANIFOLD GAS PRESSURE ADJUSTMENT
Small adjustments to the gas flow may be made by turning the
pressure regulator adjusting screw on the automatic gas valve.
Refer to Figure 6.
Adjust as follows:
1. Remove the cap from the valve body. See Figure 6 for loca-
tion.
2. To decrease the gas pressure, turn the adjusting screw
counterclockwise.
3. To increase the gas pressure, turn the adjusting screw
clockwise.
NOTE: The correct manifold pressure for natural gas furnaces
is 3.5 IWG
±
0.2. The correct manifold pressure for pro-
pane (LP) is 10.0 IWG
±
0.2.
BURNER INSTRUCTIONS
To check or change the burners, CLOSE THE MAIN MANUAL
SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE UNIT.
1. Remove the two (2) #8 screws holding each burner in
place.
2. Remove the burner assembly from the manifold assembly
by moving the burner assembly forward, turn at an angle
and pull back.
3. Burners are now accessible for service.
HOT SURFACE PILOT INSTRUCTIONS
To check, adjust or remove the hot surface pilot assembly,
CLOSE THE MAIN MANUAL SHUT-OFF VALVE AND SHUT
OFF ALL POWER TO THE UNIT.
The pilot flame should envelope
3
8
inch of the end of the flame
sensor and not contain any yellow color, see Figure 7.
To adjust the pilot flame:
1. Remove the pilot adjustment cover screw.
2. Adjust the pilot adjustment screw to achieve the proper pi-
lot flame.
3. Replace the pilot adjustment cover screw after the pilot
flame is set.
To remove the hot surface pilot assembly:
1. Disconnect the wiring from the gas valve to the hot surface
pilot assembly.
2. Remove the two (2) #8 screws holding the hot surface pilot
assembly in place.
3. Remove the hot surface pilot assembly.
To remove the hot surface ignitor and flame sensor assembly:
1. Remove the clip attaching the ignitor and sensor assembly
as shown in Figure 8.
2. Lift the pilot and sensor from the assembly. Care must be
taken not to damage the pilot or sensor when removing this
assembly.
035-18265-001-A-0202
10
Unitary Products Group
FIG. 6 - GAS VALVE
FIG. 7 - PROPER FLAME ADJUSTMENT
FIG. 8 - IGNITOR AND FLAME SENSOR ASSEMBLY
3 / 8
3
8
M A N U A L   G A S
S W I T C H
( S H O W N   I N   " O F F
P O S I T I O N )
C O N T R O L
E L E C T R I C A L
C O N N E C T I O N
I G N I T O R   E L E C T R I C A L
C O N N E C T I O N
M A N I F O L D
P R E S S U R E
T A P
G R O U N D
T E R M I N A L
1 / 2 - 1 4   N P T
( O U T L E T )
P I L O T   G A S
C O N N E C T I O N
P I L O T
A D J U S T M E N T
V E N T   P R E S S U R E   L I M I T E R
1 / 2   -   1 4   N P T
( I N L E T )
L I N E   P R E S S U R E   T A P
M A N I F O L D   P R E S S U R E
A D J U S T M E N T
( R E M O V E   C A P )