York D2NA060 User Manual

Page of 21
16
Unitary Products Group
035-18265-001-A-0202
TROUBLESHOOTING
YES
. Turn gas supply
off
Set thermostat to
SV9501
is powered
(24 VAC nominal)
Igniter warms up
and glows red
Pilot valves opens
Turn gas on.
Pilot burner lights?
Check
Line voltage power
Low voltage
transformer
Main limit
(Auto reset)
Rollout limit
(Manual reset)
Auxilary limit
(Manual reset)
Thermostat
Wiring
Air proving switch on
combustion air
blower system
Vent damper (if used)
is open and end switch
made
Unplug pilot burner cable,
measure voltage at
SV9501 HSI
terminals (24 VAC
nominal, see inset)
Replace igniter/flame rod as-
sembly
Replace SV9501
Measure voltage to SV9501.
Voltage must be at least 19.5
VAC.
Replace
SV9501
Check
transformer
line volt
supply
NO
NO
NO
NO
YES
NO
NO
Main valve opens?
System OK
Replace igniter/flame rod as-
sembly
Replace igniter/flame rod as-
sembly and retain.
Restart troubleshooting se-
quence.
Does main valve open?
Discard old igniter/flame rod
assembly
Replace
SV9501
save old
igniter/
flame rod as-
sembly for
service
YES
YES
NO
NO
INSET
START
YES
YES
NOTE: Before troubleshooting, familiarize yourself with the startup and checkout procedure.
HSI
TERMINALS