Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed 
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
TCGF60S41S1
INDOOR COIL MODEL NO.
FC/MC/PC62
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM
1600
1800
2000
ID 
DB 
(°F)
80 80
75
80
80
80 80 75
80
80 80 80
75 80 80
ID 
WB 
(°F)
57 62 62 67 72 57 62 62 67 72 57 62 62 67 72 
65
T.C.
54.5 57.8 56.7 62.8 68.7 55.3 59.1 58.5 64.7 69.7 56.1 60.4 60.2 66.6 70.7 
S.C.
54.0 49.2 40.9 40.7 32.5 56.2 52.4 43.1 42.9 34.1 58.5 55.7 45.3 45.1 35.8 
KW
2.7 2.7 2.6 2.7 2.6 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 2.7 
75
T.C.
52.7 55.6 54.4 60.5 66.0 54.8 56.8 56.1 62.1 66.9 56.9 58.0 57.7 63.7 67.9 
S.C.
52.3 48.1 39.9 39.8 31.5 54.3 51.1 42.2 41.9 33.1 56.4 54.2 44.4 44.1 34.7 
KW
3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 3.1 
85
T.C.
50.8 53.5 52.2 58.1 63.3 54.3 54.5 53.7 59.5 64.2 57.7 55.6 55.2 60.8 65.1 
S.C.
50.6 47.1 38.9 38.9 30.5 52.4 49.9 41.2 41.0 32.1 54.3 52.7 43.6 43.0 33.6 
KW
3.5 3.6 3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5 3.5 3.6 3.5 3.5 3.5 
95
T.C.
49.0 51.4 50.0 55.8 60.5 53.7 52.3 51.3 56.8 61.4 58.4 53.2 52.6 57.9 62.3 
S.C.
48.9 46.0 37.9 38.1 29.5 50.5 48.6 40.3 40.0 31.0 52.2 51.2 42.7 41.9 32.6 
KW
4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 4.0 
105
T.C.
46.4 48.2 46.9 52.5 57.0 50.0 49.3 48.1 53.3 58.0 53.7 50.4 49.3 54.2 59.0 
S.C.
46.5 44.6 36.7 36.5 28.1 48.0 47.0 39.0 38.5 29.6 49.5 49.3 41.2 40.5 31.1 
KW
4.8 4.8 4.8 4.7 4.7 4.8 4.8 4.8 4.7 4.7 4.7 4.8 4.8 4.7 4.7 
115
T.C.
43.8 45.2 43.9 49.3 53.6 46.5 46.4 45.0 50.0 54.7 49.1 47.6 46.1 50.7 55.9 
S.C.
44.1 43.3 35.5 35.0 26.8 45.5 45.4 37.6 37.1 28.3 46.9 47.5 39.8 39.2 29.7 
KW
5.6 5.6 5.7 5.4 5.4 5.5 5.5 5.6 5.4 5.3 5.5 5.5 5.5 5.4 5.3 
125
T.C.
41.3 42.2 40.8 46.0 50.2 42.9 43.5 41.9 46.6 51.5 44.5 44.9 42.9 47.2 52.7 
S.C.
41.8 41.9 34.3 33.5 25.5 43.1 43.8 36.3 35.7 26.9 44.4 45.6 38.3 37.8 28.3 
KW
6.4 6.4 6.5 6.1 6.0 6.3 6.3 6.4 6.1 6.0 6.2 6.2 6.3 6.1 6.0 
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handlers
Coils
T.C.
S.C.
KW
FC/MC/PC60
0.96
0.98
1.00
FC/MC62
1.00
1.00
1.00
HC60
0.96
0.98
1.00
AV/SV60
0.97
0.99
0.97
AHX60
1.00
0.97
0.96
F6FP060
1.00
0.97
0.92
MV20D
FC/MC60D
0.97
0.99
0.98
MA20D
FC/MC62D
1.00
1.00
1.00
MV20D
FC/MC62D
1.02
1.03
0.98
MV20D
FC64D
1.03
1.01
0.96
Furnaces
Coils
T.C.
S.C.
KW
T*(8,L)X*C16
FC/PC60C
0.97
0.95
0.95
T*(8,L)X*C20
FC/MC/PC60D
0.97
0.95
0.95
T*9X*C16
FC/PC60C
0.97
0.95
0.95
T*9X*C20
FC/PC60C
0.97
0.95
0.95
T*9X*D20
FC/MC/PC60D
0.97
0.95
0.96
T*(8,L)X*C20
FC/MC62D
0.99
0.97
0.95
T*(8,L)X*C16
FC64D
1.02
1.00
1.00
T*(8,L)X*C20
FC64D
1.03
1.03
0.99
T*9X*C16
FC64D
1.01
0.99
0.99
T*9X*C20
FC64D
1.02
1.00
0.98
T*9X*D20
FC64D
1.02
1.00
1.00
L*(8,L)C*C20 
FC/MC62D 
0.99 0.97 0.95 
(L*9C/T*9V)*C20 FC/MC62D 
0.98 0.96 0.98 
(L*9C/T*9V)*D20 FC/MC62D 
0.99 0.97 0.97 
L*(8,L)C*C16
FC64D
1.02
1.01
1.00
L*(8,L)C*C20
FC64D
1.02
1.00
0.98
(L*9C/T*9V)*C16
FC64D
1.01
0.99
0.99
(L*9C/T*9V)*C20
FC64D
1.02
1.00
1.02
(L*9C/T*9V)*D20
FC64D
1.02
1.00
1.02
(L*9C/T*9V)*D20 HC60 
0.94 0.94 0.97 
L*(8,L)C*C20 
HD60 
0.99 0.98 0.96 
(L*9C/T*9V)*C20 HD60 
1.00 0.98 0.98 
(L*9C/T*9V)*D20 HD60 
0.97 0.96 0.98