TABLE 9: COOLING CAPACITY 43.9 KW UNIT - METRIC
Air On
Evap. Coil
Temperature of Air on Condenser Coil 29°C
Temperature of Air on Condenser Coil 35°C
m
3
/s
WB
(°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
Tot.
Cap.
1
(kW)
Tot.
Input
2
(kW)
Sensible Capacity (kW)
1
Return Dry Bulb (°C)
30
28
27
25
23
22
20
30
28
27
25
23
22
20
1.77
22
44
11.8
26
23
20
17
14
-
-
42
13.0
26
23
20
16
13
-
-
19
41
11.5
34
31
27
24
21
18
15
39
12.6
33
30
26
23
20
17
14
17
36
11.2
36
34
31
28
25
21
18
34
12.4
34
33
30
27
24
20
17
14
35
11.3
35
34
31
28
25
21
18
33
12.5
33
33
29
26
23
20
17
2.06
22
46
11.8
29
26
22
18
15
-
-
43
13.0
29
25
21
18
14
-
-
19
42
11.5
37
34
30
26
23
19
15
40
12.5
36
33
29
25
21
18
14
17
37
11.2
37
36
34
30
26
23
19
35
12.4
35
35
33
29
25
22
18
14
36
11.3
36
36
34
30
26
23
19
34
12.4
34
34
32
28
25
21
17
2.36
22
47
11.8
33
28
24
20
15
-
-
45
12.9
32
28
23
19
15
-
-
19
44
11.5
41
37
33
28
24
20
15
42
12.5
40
36
31
27
23
19
14
17
39
11.3
39
39
37
32
28
24
20
37
12.3
37
37
35
31
27
23
18
14
37
11.3
37
37
37
32
28
24
20
35
12.4
35
35
35
31
26
22
18
2.65
22
48
11.9
39
34
29
24
19
-
-
46
13.1
38
33
28
23
18
-
-
19
45
11.6
44
41
39
34
30
25
20
43
12.6
42
40
38
33
28
23
18
17
39
11.3
39
39
39
34
29
24
19
38
12.5
38
38
37
32
27
22
18
14
38
11.4
38
38
38
33
28
23
18
36
12.5
36
36
36
31
26
21
16
2.95
22
49
11.9
45
39
34
28
23
-
-
47
13.2
44
38
33
27
22
-
-
19
46
11.6
46
46
46
41
35
30
24
44
12.8
44
44
44
38
33
27
22
17
40
11.4
40
40
40
35
30
24
19
39
12.6
39
39
39
33
28
22
17
14
39
11.4
39
39
39
33
28
22
17
37
12.7
37
37
37
31
26
21
15
Temperature of Air on Condenser Coil 41°C
Temperature of Air on Condenser Coil 46°C
1.77
22
39
14.3
25
22
19
16
13
-
-
37
15.6
24
21
18
15
12
-
-
19
36
13.8
32
29
25
22
19
16
13
34
15.1
31
28
24
21
18
15
12
17
32
13.6
32
32
28
25
22
19
16
30
14.9
30
30
27
24
21
18
14
14
31
13.8
31
31
28
25
21
18
15
29
15.0
29
29
26
23
20
17
13
2.06
22
41
14.3
28
24
21
17
13
-
-
38
15.6
27
23
20
16
12
-
-
19
38
13.8
35
32
28
24
20
17
13
35
15.1
34
30
27
23
19
16
12
17
33
13.6
33
33
31
27
24
20
16
31
14.9
31
31
30
26
22
18
15
14
32
13.7
32
32
30
27
23
19
15
30
15.0
30
30
28
25
21
17
14
2.36
22
42
14.3
31
27
22
18
14
-
-
40
15.6
30
26
21
17
13
-
-
19
39
13.8
38
35
30
26
22
17
13
36
15.1
36
33
29
25
21
16
12
17
34
13.6
34
34
34
30
25
21
17
32
14.9
32
32
32
28
24
19
15
14
33
13.7
33
33
33
29
24
20
16
31
15.0
31
31
31
27
22
18
14
2.65
22
43
14.4
36
31
26
21
16
-
-
40
15.7
33
29
24
19
14
-
-
19
40
13.9
40
38
35
30
25
20
15
37
15.2
37
36
32
27
22
18
13
17
35
13.7
35
35
35
30
25
20
15
33
15.0
33
33
33
28
23
18
13
14
34
13.8
34
34
34
29
24
19
14
32
15.1
32
32
32
27
22
17
12
2.95
22
44
14.5
40
35
29
24
18
-
-
41
15.8
37
32
26
21
15
-
-
19
41
14.0
41
41
40
34
29
23
18
38
15.3
38
38
35
30
24
19
13
17
36
13.8
36
36
36
31
25
20
14
34
15.0
34
34
34
28
23
17
12
14
35
13.9
35
35
35
29
24
18
13
32
15.2
32
32
32
27
21
16
10
Temperature of Air on Condenser Coil 52°C
1.77
22
35
16.9
24
20
17
14
11
-
-
19
32
16.4
30
27
23
20
17
14
11
17
28
16.1
28
28
26
22
19
16
13
14
27
16.3
27
27
24
21
18
15
12
2.06
22
36
16.9
26
23
19
15
11
-
-
19
33
16.4
32
29
26
22
18
15
11
17
29
16.1
29
29
28
24
21
17
13
14
28
16.3
28
28
27
23
19
16
12
2.36
22
37
16.9
29
25
21
16
12
-
-
19
34
16.4
34
32
28
24
19
15
11
17
30
16.1
30
30
30
26
22
18
13
14
29
16.3
29
29
29
25
20
16
12
2.65
22
37
17.0
31
27
22
17
12
-
-
19
34
16.5
34
34
29
25
20
15
10
17
31
16.2
31
31
31
26
21
16
11
14
29
16.4
29
29
29
25
20
15
10
2.95
22
38
17.1
34
28
23
17
12
-
-
19
35
16.5
35
35
31
26
20
15
9
17
31
16.3
31
31
31
26
20
15
9
14
30
16.5
30
30
30
24
19
14
8
1 These capacities are gross ratings.  For net 
capacity, deduct air blower motor, MBh = 3.415 
x kW.  Refer to the appropriate Blower 
Performance Table for the kW of the supply air 
blower motor.
2 These ratings include condenser fan motors  
and the compressor motors but not the supply 
air blower motor.