5
Wide Range of Indoor Airflows – All indoor fan motors 
are belt-drive type providing maximum flexibility to han-
dle most airflow requirements.  For high static applica-
tions, factory installed alternate indoor fan motors are 
available.  With the optional indoor fan motor, all units 
can supply nominal airflow at a minimum of 1.5” (375 Pa) 
ESP.
FACTORY INSTALLED OPTIONS
YORK
®
 offers several equipment options factory installed, for 
the Predator
®
 line.
Downflow Economizer (With barometric relief) - The 
economizer is provided with a single enthalpy input. The 
economizer is 2% low leakage type, and is shipped 
installed and wired. The installer needs only to assemble 
and mount the outdoor air hood (Provided). The econo-
mizer has spring return, fully modulating damper actua-
tors and is capable of introducing up to 100% outdoor air. 
As the outdoor air intake dampers open, the return air 
dampers close. The changeover from mechanical refrig-
eration to economizer operation is regulated by the stan-
dard single enthalpy input. There is an optional input 
dual dry bulb available. To meet regulated air standards, 
the economizer control accepts an optional CO
2
 
input for
 
demand ventilation. With single enthalpy input, the econ-
omizer control monitors outdoor air. The dual enthalpy kit 
provides a second input used to monitor the return air. 
With a dual input kit installed, the economizer control 
compares the values of the two enthalpy or temperature 
inputs and positions the dampers to provide the maxi-
mum efficiency possible.
Horizontal Economizer (Without barometric relief) 
All features as the downflow economizer exist except 
you must order the barometric relief separately. You 
must order a 1EH0408 if you are installing a power 
exhaust. You can order a 1RD0411 Barometric Relief 
for horizontal flow economizers only.
 BAS Ready Economizer -(With barometric relief) 
The economizer is provided with a Belimo actuator that 
requires a 0-10V DC input from an external source (i.e., 
field installed building automation system controller). 
Power exhaust options are available. The economizer is 
2% low leakage type with spring return and fully modu-
lating dampers capable of introducing up to 100% out-
side air. Also include 2” (51 mm) pleated filters.
Power Exhaust (Downflow only) - This accessory 
installs in the unit with a down flow economizer. 
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper 
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the 
indoor fan motor is energized. The damper has a range 
of 0% to 100% outdoor air entry. Factory installed option 
or field installed accessory.
Alternate Indoor Blower Motor - For applications with 
high static restrictions, units are offered with optional 
indoor motors that provide higher static output and/or 
higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For applica-
tions in non-corrosive environments. 
Stainless Steel Gas Heat Exchanger - For applications 
in corrosive environments, this option provides a full 
stainless steel heat exchanger assembly.
Electric Heaters - The electric heaters range from 9kW 
to 54kW and are available in all the voltage options of the 
base units. All heaters are dual staged. All heaters are 
intended for single point power supply.
Disconnect Switch - For gas heat units and cooling 
units with electric heat, a HACR breaker sized to the unit 
is provided. For cooling only units, a switch sized to the 
largest electric heat available for the particular unit is 
provided. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation 
of the unit by interrupting power to the control board if 
smoke is detected within the air compartment. Available 
for both the supply and/or return air.
Phase Monitors - Designed to prevent unit damage. 
The phase monitor will shut the unit down in an out-of 
phase condition. (Standard on units with Scroll Com-
pressors.)
Coil Guard - Customers can purchase a coil guard kit to 
protect the condenser coil from damage. Additionally, 
this kit stops animals and foreign objects from entering 
the space between the inner condenser coil and the 
main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high 
pressure drop across the filters. Factory installed option 
or field installed accessory.
Technicoat Condenser Coils - The condenser coils are 
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are 
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
Novar® BAS Control - The Novar® ETC-3 building 
automation system controller is factory installed. Incudes 
supply air sensor, return air sensor, dirty filter indicator 
switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control 
YK-UNT-1126 building automation system controller is 
factory installed. Includes supply air sensor, return air 
sensor, dirty filter indicator switch, and air proving switch.