York DNP042 User Manual

Page of 36
 036-21366-007-A-1205
16
Unitary Products Group
   
TABLE 10: SIDE SUPPLY AIR BLOWER PERFORMANCE - 208/230 VOLTS
1
MODEL # 
DNP
MODE 
(COOLING / HEATING)
CFM
EXTERNAL STATIC PRESSURE - IWG
.20
.30
.40
.50
.60
.70
.80
.90
1.0
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
WATTS
030
COOLING
(FACTORY SETTING) 
1000
248
298
325
365
385
411
470
498
500
030 
COOLING
(FIELD SETTING) 
1250
342
385
431
474
510
562
614
657
694
030 
HEATING (2 TUBE)
(FACTORY SETTING) 
850
169
217
237
278
302
334
374
401
431
030 
HEATING (3 TUBE)
(FACTORY SETTING) 
1100
300
338
378
416
447
493
539
576
609
036 
COOLING
(FACTORY SETTING) 
1200
354
396
436
511
548
599
641
677
721
036 
COOLING
(FIELD SETTING) 
1350
442
503
563
606
648
685
721
774
826
036 
HEATING (2 TUBE)
(FACTORY SETTING) 
700
207
231
254
298
320
349
- - - 
036 
HEATING (3 TUBE)
(FACTORY SETTING) 
1250
383
432
478
543
581
628
- - - 
036 
HEATING (4 TUBE)
(FACTORY SETTING) 
1350
442
503
563
606
648
685
- - - 
042 
COOLING
(FACTORY SETTING) 
1350
410
457
504
575
646
687
729
780
830
042 
COOLING
(FIELD SETTING) 
1500
450
500
553
641
729
798
830
872
939
042 
HEATING (3 TUBE)
(FACTORY SETTING) 
1500
450
500
553
641
729
798
830
872
939
042 
HEATING (4 TUBE)
(FACTORY SETTING) 
1275
388
433
478
545
612
652
691
739
787
048 
COOLING
(FACTORY SETTING) 
1400
427
476
525
599
673
716
759
812
865
048 
COOLING
(FIELD SETTING) 
1600
476
532
587
687
786
872
958
994
1030
048 
HEATING (3 TUBE)
(FACTORY SETTING) 
1525
458
511
564
654
744
814
- - - 
048 
HEATING (4 TUBE)
(FACTORY SETTING) 
1600
476
532
587
687
786
872
- - - 
048 
HEATING (5 TUBE)
(FACTORY SETTING) 
1600
476
532
587
687
786
872
- - - 
060
COOLING
(FACTORY SETTING) 
1500
439
526
559
636
716
748
816
884
941
060
COOLING
(FIELD SETTING) 
1800
659
809
814
946
1001
1053
1124
1176
1180
060
HEATING (3 TUBE)
(FACTORY SETTING) 
1500
439
526
559
636
716
748
816
884
941
060
HEATING (4 TUBE)
(FACTORY SETTING) 
1700
576
757
788
872
929
979
1000
1121
1188
060
HEATING (5 TUBE)
(FACTORY SETTING) 
1700
576
757
788
872
929
979
1000
1121
1188
1.
Above data includes allowances for a dry coil, gas heat exchanger and no filters. For additional pressure drops, refer to Tables 11 
and 12.