York DNP042 User Manual

Page of 36
036-21366-007-A-1205
Unitary Products Group
7
TABLE 2: RATINGS COOLING/GAS HEATING
MODEL
DNP
NET COOLING CAPACITY
1
SOUND
RATING
(dbels)
2
GAS HEAT CAPACITY / EFFICIENCIES
MBH
SEER
3
EER
4
INPUT
(MBH)
OUTPUT
(MBH)
AFUE
5
(%)
NUMBER OF
BURNERS
TEMP.
RISE
(°F) RANGE
024N03606
25.4
13.3
11.6
81
45
36
80.2
2
25 - 55
024N05606
25.4
13.3
11.6
81
70
56
80.2
3
30 - 60
030N03606
30.6
13.4
11.75
80
45
36
80.2
2
25 - 55
030N03625
30.6
13.4
11.75
80
45
36
80.2
2
25 - 55
030N03646
30.6
13.4
11.75
80
45
36
80.2
2
25 - 55
030N05606
30.6
13.4
11.75
80
70
56
80.2
3
30 - 60
030N05625
30.6
13.4
11.75
80
70
56
80.2
3
30 - 60
030N05646
30.6
13.4
11.75
80
70
56
80.2
3
30 - 60
036N03606
37.4
13.65
11.75
81
45
36
80.4
2
25 - 55
036N03625
37.4
13.65
11.75
81
45
36
80.4
2
25 - 55
036N03646
37.4
13.65
11.75
81
45
36
80.4
2
25 - 55
036N03658
37.4
13.65
11.75
81
45
36
80.4
2
25 - 55
036N05606
37.4
13.65
11.75
81
70
56
80.2
3
25 - 55
036N05625
37.4
13.65
11.75
81
70
56
80.2
3
25 - 55
036N05646
37.4
13.65
11.75
81
70
56
80.2
3
25 - 55
036N05658
37.4
13.65
11.75
81
70
56
80.2
3
25 - 55
036N07206
37.4
13.65
11.75
81
90
72
80.1
4
30 - 60
036N07225
37.4
13.65
11.75
81
90
72
80.1
4
30 - 60
036N07246
37.4
13.65
11.75
81
90
72
80.1
4
30 - 60
036N07258
37.4
13.65
11.75
81
90
72
80.1
4
30 - 60
042N06506
44
13.7
10.65
80
80
64
80.6
3
25 - 55
042N06525
44
13.7
10.65
80
80
64
80.6
3
25 - 55
042N06546
44
13.7
10.65
80
80
64
80.6
3
25 - 55
042N06558
44
13.7
10.65
80
80
64
80.6
3
25 - 55
042N09006
44
13.7
10.65
80
108
86
80.8
4
45 - 75
042N09025
44
13.7
10.65
80
108
86
80.8
4
45 - 75
042N09046
44
13.7
10.65
80
108
86
80.8
4
45 - 75
042N09058
44
13.7
10.65
80
108
86
80.8
4
45 - 75
048N06506
48
13.2
11.7
84
80
64
80.8
3
25 - 55
048N06525
48
13.2
11.7
84
80
64
80.8
3
25 - 55
048N06546
48
13.2
11.7
84
80
64
80.8
3
25 - 55
048N06558
48
13.2
11.7
84
80
64
80.8
3
25 - 55
048N09006
48
13.2
11.7
84
108
86
80.6
4
35 - 65
048N09025
48
13.2
11.7
84
108
86
80.6
4
35 - 65
048N09046
48
13.2
11.7
84
108
86
80.6
4
35 - 65
048N09058
48
13.2
11.7
84
108
86
80.6
4
35 - 65
048N11006
48
13.2
11.7
84
135
107
80.5
5
45 - 75
048N11025
48
13.2
11.7
84
135
107
80.5
5
45 - 75
048N11046
48
13.2
11.7
84
135
107
80.5
5
45 - 75
048N11058
48
13.2
11.7
84
135
107
80.5
5
45 - 75
060N06506
55.5
13.0
11.2
84
80
64
80.8
3
25 - 55
060N06525
55.5
13.0
11.2
84
80
64
80.8
3
25 - 55
060N06546
55.5
13.0
11.2
84
80
64
80.8
3
25 - 55
060N06558
55.5
13.0
11.2
84
80
64
80.8
3
25 - 55
060N09006
55.5
13.0
11.2
84
108
86
80.6
4
35 - 65
060N09025
55.5
13.0
11.2
84
108
86
80.6
4
35 - 65
060N09046
55.5
13.0
11.2
84
108
86
80.6
4
35 - 65
060N09058
55.5
13.0
11.2
84
108
86
80.6
4
35 - 65
060N11006
55.5
13.0
11.2
84
135
107
80.5
5
45 - 75
060N11025
55.5
13.0
11.2
84
135
107
80.5
5
45 - 75
060N11046
55.5
13.0
11.2
84
135
107
80.5
5
45 - 75
060N11058
55.5
13.0
11.2
84
135
107
80.5
5
45 - 75
1.
Net Cooling Capacity = ARI 210 standard rating conditions.
2.
(dbels) = ARI 270-95
3.
Seasonal Energy Efficiency Ratio - the total cooling output in BTU’s during a normal annual usage period for cooling divided by the 
total electric power input in watt-hours during the same period.
4.
Tested in accordance with ARI 210 Standard Rating Conditions.
5.
AFUE = Annual Fuel Utilization Efficiency.