York D7CG 060 User Manual

Page of 20
UNIT
SIZE
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
072
3200
1150
2325
1182
2425
1212
2525
-
-
-
-
-
-
-
-
3000
1100
2010
1129
2090
1157
2150
1185
2225
1215
2290
1242
2360
-
-
2800
1045
1700
1074
1780
1102
1850
1131
1940
1160
2025
1190
2075
1217
2130
2600
985
1425
1015
1475
1045
1540
1075
1630
1103
1715
1135
1760
1163
1825
2400
930
1240
958
1300
990
1350
1020
1400
1051
1430
1081
1490
1111
1600
2200
-
-
905
1070
933
1160
965
1210
997
1250
1028
1285
1060
1325
2000
-
-
-
-
-
-
919
1025
950
1100
982
1130
1014
1160
1800
-
-
-
-
-
-
-
-
909
925
939
1005
968
1030
6 TON - SIDE DUCT CONNECTIONS @ 230/460/575 Volts
UNIT
SIZE
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.90
1.00
1.10
1.20
1.30
1.40
1.50
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
072
3200
-
-
-
-
-
-
-
-
-
-
-
-
-
-
3000
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2800
1245
2190
-
-
-
-
-
-
-
-
-
-
-
-
2600
1193
1920
1222
1990
1250
2060
-
-
-
-
-
-
-
-
2400
1142
1675
1173
1730
1205
1800
1234
1885
-
-
-
-
-
-
2200
1090
1380
1124
1450
1155
1550
1186
1640
1217
1710
1249
1775
-
-
2000
1045
1175
1077
1200
1109
1275
1140
1360
1170
1460
1205
1545
1235
1600
1800
998
1050
1028
1060
1058
1060
1087
1075
1118
1150
1148
1250
1176
1360
NOTE:  FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*
INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS, AND GAS-FIRED HEAT EXCHANGERS. REFER TO  TABLE 8 FOR RESISTANCE VALUES ON CONNECTIONS
OTHER THAN  SIDE DUCT AIRFLOWS.
- SUPPLY AIR  PERFORMANCE - 5 & 6 Ton w/Belt-Drive Blower
TABLE 9
UNIT
SIZE
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.20
0.30
0.40
0.50
0.60
0.70
0.80
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
060
2500
1059
1560
1077
1590
1095
1630
1114
1650
1134
1660
1158
1685
1181
1720
2400
1032
1405
1054
1470
1074
1525
1094
1560
1116
1595
1140
1620
1167
1640
2300
1005
1260
1024
1275
1049
1370
1069
1440
1090
1475
1116
1505
1142
1535
2200
980
1160
1002
1170
1022
1190
1044
1250
1066
1350
1090
1410
1117
1440
2100
930
1060
957
1070
983
1080
1010
1100
1039
1160
1064
1260
1092
1340
2000
877
950
908
975
941
1000
976
1020
1009
1050
1040
1100
1070
1225
1900
-
-
-
-
894
885
940
940
980
980
1014
1020
1047
1095
1800
-
-
-
-
855
815
903
860
950
905
988
940
1022
970
1700
-
-
-
-
-
-
884
815
925
850
964
880
1001
910
1600
-
-
-
-
-
-
864
770
908
805
948
835
987
870
1500
-
-
-
-
-
-
-
-
882
740
926
780
965
830
5 TON - SIDE DUCT CONNECTIONS @ 230/460/575 Volts
UNIT
SIZE
AIR FLOW
CFM
Available External Static Pressure - IWG*
0.90
1.00
1.10
1.20
1.30
1.40
1.50
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
RPM
Watts
060
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
1193
1665
-
-
-
-
-
-
-
-
-
-
-
-
2300
1170
1580
1202
1620
-
-
-
-
-
-
-
-
-
-
2200
1148
1480
1180
1530
-
-
-
-
-
-
-
-
-
-
2100
1121
1385
1155
1425
1190
1475
-
-
-
-
-
-
-
-
2000
1100
1285
1133
1340
1169
1385
1205
1445
-
-
-
-
-
-
1900
1079
1180
1110
1240
1143
1280
1178
1330
1222
1375
-
-
-
-
1800
1058
1060
1090
1135
1122
1190
1158
1240
1196
1295
-
-
-
-
1700
1035
960
1071
1030
1103
1100
1134
1140
1164
1175
1197
1205
-
-
1600
1020
900
1056
965
1088
1035
1118
1065
1145
1105
1170
1130
1198
1150
1500
1004
860
1038
880
1070
925
1101
980
1130
1045
1158
1075
1184
1110
NOTE:  FOR 208 VOLTS, MULTIPLY VALUES BY 0.95.
*
INCLUDES ALLOWANCES FOR A WET EVAPORATOR COIL, 1" FILTERS, AND GAS-FIRED HEAT EXCHANGERS. REFER TO  TABLE 8 FOR RESISTANCE VALUES ON CONNECTIONS
OTHER THAN  SIDE DUCT AIRFLOWS.
530.18-N8Y
Unitary Products Group
11