OPTIONAL OUTDOOR AIR
(Shall be made available by either/or):
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55 ºF. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.
2. DUAL INPUT DIFFERENTIAL ELECTRONIC 
ENTHALPY AUTOMATIC ECONOMIZER - Outdoor and 
return air dampers that are interlocked and positioned by 
a fully-modulating, spring-return damper actuator. The 
maximum leakage rate for the outdoor air intake damp-
ers shall not exceed 2% when dampers are fully closed 
and operating against a pressure differential of 0.5 IWG. 
A unit mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in 
the design CFM of outdoor air to meet the minimum ven-
tilation requirement of the conditioned space during nor-
mal operation. During economizer operation, a mixed-air 
temperature control shall modulate the outdoor and 
return air damper assembly to prevent the supply air 
temperature from dropping below 55 ºF. Changeover 
from compressor to economizer operation shall be pro-
vided by two integral electronic enthalpy controls - one 
that senses outdoor air and one that senses indoor air. 
Both enthalpy sensors supply input to the logic module 
which modulates both sets of dampers for maximum 
economizer savings. The outdoor intake opening shall 
be covered with a rain hood that matches the exterior of 
the unit. Water eliminator/filters shall be provided. Simul-
taneous economizer/compressor operation is also possi-
ble. Dampers shall fully close on power loss.
OTHER PRE-ENGINEERED ACCESSORIES AVAIL-
ABLE
1. ROOF CURB - 14" AND 8" high, full perimeter knock-
down curb with hinged design for quick assembly.
2. MANUAL OUTDOOR DAMPER - Provides 0% through 
35% or 0% through 100% outdoor air capability (field 
adjustable). Designed for duct mounted side supply/
return applications. Includes a hood and a screen 
assembly.
3. OUTDOOR COIL GUARD - Prevents coil damage.
4. BAROMETRIC RELIEF DAMPER - Contains a rain 
hood, air inlet screen, exhaust damper and mounting 
hardware. Used to relieve internal air pressure through 
the unit during economizer operation.
5. PROPANE CONVERSION KIT - Contains new orifices 
and gas valve regulator to convert from natural to L.P. 
gas.
6. LOW NOX - Required to reduce the emission of nitrogen 
oxides below 40 nano grams per joule.
7. HIGH ALTITUDE - NATURAL GAS - Required for appli-
cations between 2000 and 6000 feet altitude.
8. HIGH ALTITUDE - PROPANE GAS - Required for appli-
cations between 2000 and 6000 feet altitude. Must be 
used with propane conversion kit.
9. GAS PIPING - Contains pipe nipples, fittings and gas 
cock (including panel assess gaskets) required for bot-
tom gas supply connection with external shut-off.
10. BURGLAR BARS - Designed to work with above 
roofcurbs. Fits duct openings of curb supply and return 
air openings.
11. THERMOSTATS - Multiple models available from 
A.C.O., M.C.O., Electronic or Electrical Mechanical ver-
sions.
12. ANTI-RECYCLE TIMER - Assures 5-minute off-time 
between compressor cycles.
13. LOW AMBIENT KIT - Provides unit cooling operation 
down to 0 ºF.
14. ELECTRIC HEAT - Slide-in design, provides single point 
power and ranges from 5 to 30 KW.
OTHER FACTORY INSTALLED OPTIONS
1. HIGH PERFORMANCE BELT DRIVE MOTOR
2. TECHNICOAT PHENOLIC COATED COND. COIL
3. ELECTRONIC ENTHALPY ECONOMIZER
4. DUAL INPUT ELECTRONIC ENTHALPY ECONO-
MIZER