Model
HCE
Voltage
Code
Compressor
Condenser Fan Motor
Unit
Ampacity
(Amps)
Max.
Fuse
Size
1
(Amps)
Power
Supply
RLA
LRA
Power
Supply
HP
Qty.
FLA
090
25
208/230-3-60
25.6
190
208/230-1-60
3/4
1
3.03
35.1
60
46
460-3-60
12.8
95
460-1-60
3/4
1
1.6
17.6
30
58
575-3-60
10.2
75
575-1-60
3/4
1
1.8
14.6
20
120
25
208/230-3-60
42.0
239
208/230-1-60
1/2
2
2.7
51.8
70
46
460-3-60
19.2
125
460-1-60
1/2
2
1.6
24.7
35
58
575-3-60
13.8
80
460-1-60
2
1/2
2
1.3
18.0
25
150
25
208/230-3-60
41.4
312
208/230-1-60
1/2
2
3.0
52.6
70
46
460-3-60
20.0
150
460-1-60
1/2
2
1.8
26.1
35
58
575-3-60
16.4
108
460-1-60
2
1/2
2
1.8
21.3
30
1
Dual element.
2
Unit includes a 575 to 460-volt transformer.
TABLE 3 - ELECTRICAL DATA
 
          
 
 
 
 
 
  !" # $ %& '(%%')" )( )*
"+,,- )$, %.!* (%  '.% /
$(+)" " $')!- $(, ) '(%"%* %&
+% ) )( ) )$,(*).)   "* $"0
  
12  3
 
31  
 
  3
11 
NOTE
:
USE COPPER
CONDUCTORS ONLY
WIRE IN ACCORDANCE WITH
ALL LOCAL AND NATIONAL
ELECTRICAL CODES
S
IZE POWER WIRING,
DISCONNECT SWITCH, AND
FUSING PER ELECTIRICAL
DATA TABLE
FIG. 3 - TYPICAL FIELD WIRING WITH KES/KEU AIR HANDLER
TERMINAL STRIP
TB1 ON
HEHB090
24-VOLT
ISOLATION RELAY
(FIELD SUPPLIED)
THERMOSTAT*
TERMINALS
TERMINAL STRIP
ON FURNACE
*24-volt thermostat
2TH13700424 with Subbase 2TB17700424.
R
Y1
B
R
Y
G
W
R
Y
G
W
C
COIL
PMUB30N19031
FIG. 4 - TYPICAL WIRING WITH PUC  FURNACE