York YZB018 THRU 060 User Manual

Page of 40
Subject to change without notice. Printed in U.S.A.
271457-YTG-B-0908 
Copyright © 2008 by Johnson Controls, Inc. All rights reserved. 
Supersedes: 271457-YTG-A-0907
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
Multipliers for determining the performance with other indoor sections.
HEATING PERFORMANCE DATA
OUTDOOR UNIT MODEL NO.
YZB06012
INDOOR COIL MODEL NO.
FC/MC62D
AIR TEMP.
ENTERING
OUTDOOR UNIT
AIR TEMP.
ENTERING
INDOOR COIL
ID CFM
1650
1900
2150
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
MBTUH
KW
C.O.P.
60
60
71.5 4.9  4.3 72.1 4.8  4.4 72.7 4.6  4.6 
70
70.3 5.4  3.8 70.9 5.3  3.9 71.5 5.1  4.1 
80
69.2 5.9  3.4 69.8 5.8  3.5 70.3 5.6  3.7 
47
60
61.1 4.8  3.8 61.2 4.7  3.8 61.4 4.6  3.9 
70
60.3 5.3  3.4 60.6 5.2  3.4 60.8 5.1  3.5 
80
59.6 5.8  3.0 59.9 5.7  3.1 60.2 5.6  3.2 
40
60
53.5 4.7  3.3 50.2 4.6  3.2 47.0 4.6  3.0 
70
53.7 5.3  3.0 52.0 5.1  3.0 50.4 5.0  3.0 
80
53.9 5.9  2.7 53.8 5.6  2.8 53.8 5.4  2.9 
30
60
43.9 4.6  2.8 42.5 4.5  2.8 41.1 4.5  2.7 
70
44.0 5.2  2.5 42.6 5.1  2.4 41.1 5.1  2.4 
80
44.2 5.8  2.2 42.7 5.7  2.2 41.2 5.6  2.1 
17
60
35.4 4.4  2.4 35.0 4.3  2.4 34.6 4.3  2.4 
70
35.0 4.9  2.1 35.3 4.9  2.1 35.7 4.8  2.2 
80
34.5 5.4  1.9 35.7 5.4  1.9 36.8 5.4  2.0 
10
60
30.7 4.4  2.1 28.9 4.3  2.0 27.2 4.3  1.9 
70
30.9 4.9  1.8 30.0 4.9  1.8 29.1 4.9  1.8 
80
31.1 5.5  1.7 31.0 5.4  1.7 31.0 5.4  1.7 
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler
Coil
MBH
KW
COP
MV20D 
FC/MC62D 
1.00 1.01 0.99 
MA20D 
FC/MC62D 
1.00 1.00 1.00 
Variable Speed 
Furnace
Coil
MBH
KW
COP
P(C,V)9*D20
FC/MC62D 
0.96 1.01 0.99 
Y*(8,L)C*C20 
FC/MC62D 
0.98 1.00 0.98 
Y*9C*C20 
FC/MC62D 
0.99 0.99 1.00 
Y*9C*D20 
FC/MC62D 
0.99 0.99 1.00 
G*9V*C20 
FC/MC62D 
0.99 0.99 1.00 
G*9V*D20 
FC/MC62D 
0.99 0.99 1.00