York DY 048 User Manual

Page of 36
343615-YTG-B-0308
8
Johnson Controls Unitary Products
ENTHALPY ACCESSORY CONTROL KIT - This kit 
contains the required components to convert a single 
enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return 
openings to prevent entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with 
wind or weather conditions which may interfere with 
proper exhausting of furnace combustion products, this 
kit can be installed to prevent the flue exhaust from 
entering nearby fresh air intakes.
CO
2
 SENSOR - Senses CO
2
 levels and automatically 
overrides the economizer when levels rise above the 
present limits.
COIL GUARD - Customers can purchase a coil guard kit 
to protect the condenser coil from damage. This is not a 
hail guard kit.
HAIL GUARD - Hail Guard kit is available to prevent unit 
from hail damage. This is a sloped hood that fits above 
the coil.
GAS PIPING KIT - This kit supplies all necessary fittings 
and shut off valve.
TABLE 1:
CAPACITY RATINGS - (ARI 210/240)
1
1. 80/67°F Indoor and 95°F outdoor.
MODEL
MBH
EER
2
2. EER = Energy Efficiency Ratio at full load - the cooling 
capacity in Btu’s per hour (Btuh) divided by the power 
input in watts, expressed in Btuh per watt (Btuh/watt).
SEER
3
3. SEER = Seasonal Energy Efficiency Ratio.
CFM
SOUND 
RATING
 (Db)
4
4. Rated in accordance with ARI 270 Standard.
DY036
35.6
12
14
1200
84
DY048
46.0
12
14
1600
83
DY060
59.0
11.6
14
1750
81
TABLE 2:
GAS HEAT RATINGS
1
1. All units are single-stage heating. 
MODEL
MBH 
INPUT
MBH 
OUTPUT
AFUE 
(%)
TEMP 
RISE ºF
DY036N04
DY036N08
50
100
40
80
80.9
80.5
15 - 45
45 - 75
DY048N06
DY048N10
75
125
60
100
80.9
80.3
25 - 70
45 - 75
DY060N08
DY060N10
100
125
80
100
80.5
80.3
25 - 55
30 - 75
TABLE 3:
2 STAGE GAS HEAT RATINGS
MODEL
1
1. Models are 3Ø only.
MBH INPUT
MBH OUTPUT
STEADY STATE EFFICIENCY
RISE
MINIMUM HEATING
AIRFLOW (CFM)
1
ST
 STAGE 2
ND
 STAGE 1
ST
 STAGE 2
ND
 STAGE
1
ST
 STAGE
2
ND
 STAGE
MIN.
MAX.
 DY036D06
45
75
35.8
60.8
79.4
81.1
35
70
790
 DY036D10
69
115
55.2
92
80.0
80.2
55
90
950
 DY048D06
45
75
35.7
60.8
79.4
81.1
25
70
790
 DY048D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
 DY060D06
45
75
35.8
60.8
79.4
81.1
20
55
1010
 DY060D10
75
125
60.4
100.6
80.5
80.5
35
75
1230