Physical and Electrical Data
MODEL
HABE-F018S HDBE-F024S HCBE-F030S HABE-F036S HBBE-F042S HBBE-F048S HCBE-F060S
Unit Supply Voltage
208-230V, 1
φ, 60Hz
Normal Voltage Range
1
187 to 252
Minimum Circuit Ampacity
8.5
10.5
16.9
18.1
17.8
20.6
33.5
Max. Overcurrent Device Amps 
2
15
15
25
25
30
35
50
Min. Overcurrent Device Amps 
3
15
15
20
20
20
25
35
Compressor Type
Recip
Recip
Recip
Scroll
Scroll
Scroll
Scroll
Compressor Amps
Rated Load
6.4
8.0
12.8
13.5
13.2
15.5
25.6
Locked Rotor
36
40.5
68
73
95
109
150
Crankcase Heater
No
No
No
No
No
No
No
Fan Motor Amps
Rated Load
0.5
0.5
0.8
1.5
1.5
1.5
1.5
Fan Diameter Inches
22
22
22
22
24
24
24
Fan Motor
Rated HP
1/15
1/15
1/8
1/4
1/4
1/4
1/4
Nominal RPM
830
830
1075
850
850
850
850
Nominal CFM
2,100
2,000
2,800
3,300
3,300
3,300
3,600
Coil
Face Area Sq Ft
15.71
15.71
23.58
23.58
22.50
27.00
27.00
Rows  Deep
1
1
1
1
2
2
2
Fin /Inch
22
22
22
18
18
18
18
Liquid Line Set OD (Field Installed)
3/8
3/8
3/8
3/8
3/8
3/8
3/8
Vapor Line Set OD (Field Installed)
3/4
3/4
7/8
7/8
1 1/8
1 1/8
1 1/8
Unit Charge (Lbs - Oz)
4
5 - 9
6 - 0
8 - 2
9 - 14
14 - 15
15 - 5
16 - 5
Charge Per Foot, oz.
0.68
0.68
0.70
0.68
0.76
0.76
0.76
Operating Weight Lbs
170
181
193
219
240
264
279
1. Rated in accordance with ARI Standard 110, utilization range “A”.
2. Dual element fuses or HACR circuit breaker. Maximum allowable overcurrent protection.
3. Dual element fuses or HACR circuit breaker. Minimum recommended overcurrent protection.
4. The Unit Charge is correct for the outdoor unit, matched indoor coil and 15 feet of refrigerant tubing.  For tubing lengths other than 15 
feet, add or subtract the amount of refrigerant, using the difference in length multiplied by the per foot value.
A
B
C
Unit
Model
Dimensions
(Inches)
Refrigerant Connection
Service Valve Size
A
1
1. Included Fan Guard.
* Adapter fitting required for 1-1/8” line set.
B
C
Liquid
Vapor
018
27
37
27
3/8
3/4
024
27
37
27
030
39
37
27
7/8
036
39
37
27
042
32
43
32
1-1/8
048
38
43
32
060
38
43
32
7/8*