York DH 300 User Manual

Page of 44
262260-YTG-E-1008
Johnson Controls Unitary Products
29
 
NOTE 1:  HACR Type per NEC.
 
NOTE 1:  HACR Type per NEC.
TABLE 20: DH 300 ELECTRICAL DATA STANDARD MOTOR WITHOUT POWERED CONVENIENCE OUTLET
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID 
BLOWER 
MOTOR 
FLA
CONV
OUTLET 
AMPS
HEATER OPTION
MIN.
CIRCUIT
 AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
300
(25)
208
37.1
239
4.5
28.0
0.0
None
-
-
-
120.5
150
E18
13.5
1
37.5
120.5
150
E36
27.0
2
74.9
128.7
150
E54
40.6
2
112.7
175.9
200
E72
54.1
2
150.2
185.2
200
230
37.1
239
4.3
26.0
0.0
None
-
-
-
118.1
150
E18
18.0
1
43.3
118.1
150
E36
36.0
2
86.6
140.8
150
E54
54.0
2
129.9
162.4
175
E72
72.0
2
173.2
205.7
225
460
17.2
125
2.2
13.0
0.0
None
-
-
-
56.1
70
E18
18.0
1
21.7
56.1
70
E36
36.0
2
43.3
70.4
80
E54
54.0
2
65.0
81.2
90
E72
72.0
2
86.6
102.9
110
575
12.4
80
1.7
10.0
0.0
None
-
-
-
41.3
50
E18
18.0
1
17.3
41.3
50
E36
36.0
2
34.6
55.8
60
E54
54.0
2
52.0
64.5
70
E72
72.0
2
69.3
81.8
90
TABLE 21: DH 300 ELECTRICAL DATA HIGH STATIC MOTOR WITHOUT POWERED CONVENIENCE OUTLET
MODEL
(TON-
NAGE)
VOLTAGE
COMPRESSORS
OD FAN
MOTORS
FLA EACH
ID 
BLOWER 
MOTOR 
FLA
CONV
OUTLET 
AMPS
HEATER OPTION
MIN.
CIRCUIT
 AMPACITY
(AMPS)
MAX.
FUSE/
BRKR
1
SIZE
(AMPS)
RLA
EACH
LRA
EACH
MODEL
KW
STAGES
AMPS
300
(25)
208
37.1
239
4.5
38.6
0.0
None
-
-
-
131.5
150
E18
13.5
1
37.5
131.5
150
E36
27.0
2
74.9
141.9
150
E54
40.6
2
112.7
189.1
200
E72
54.1
2
150.2
198.4
225
230
37.1
239
4.3
38.6
0.0
None
-
-
-
131.1
150
E18
18.0
1
43.3
131.1
150
E36
36.0
2
86.6
156.5
175
E54
54.0
2
129.9
178.2
200
E72
72.0
2
173.2
221.5
250
460
17.2
125
2.2
19.3
0.0
None
-
-
-
62.9
80
E18
18.0
1
21.7
62.9
80
E36
36.0
2
43.3
78.3
80
E54
54.0
2
65.0
89.1
100
E72
72.0
2
86.6
110.7
125
575
12.4
80
1.7
15.4
0.0
None
-
-
-
47.5
60
E18
18.0
1
17.3
47.5
60
E36
36.0
2
34.6
62.6
70
E54
54.0
2
52.0
71.2
80
E72
72.0
2
69.3
88.5
100