TABLE 25: DH VOLTAGE LIMITATIONS
1
1. Utilization Range “A” in accordance with ARI Standard 
110.
POWER SUPPLY
VOLTAGE
MIN.
MAX.
208/230-3-60
187
253
460-3-60
414
506
575-3-60
518
506
TABLE 26: ELECTRIC HEAT CORRECTION 
FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTI-
PLIER
208
208
1.00
240
230
0.92
480
460
0.92
600
575
0.92
FIGURE 3 -
TYPICAL DH FIELD WIRING DIAGRAM
RH
RC
Y1
Y2
W1
W2
G
R
RH
Y1
Y2
W1
W2
G
B
LED1
LED2
COM
A1
A2
T
T
4
4
3
3
Y1
Y2
W1
W2
G
B
X
A1
A2
L1
L3
L2
RC
R
Y1
Y2
W1
W2
G
B
X
A1
A2
Y3
NOT USED
TO REMOTE SENSOR 
2THO4702224 IF USED
1
Electronic programmable thermostat 2ET04700224 (includes subbase). 
2
Terminal block 1TB- located on relay board in 24-volt section of the unit control box. 
3
Second stage heating is not required on units with a single stage electric heater. 
4
Terminals A1 and A2 provide a relay output to close the outdoor economizer dampers 
  when the thermostat switches to the set-back position. 
NOTE: Fans switch must be in "ON" position for minimum ventilation during heater operation.
LINE VOLTAGE 
TERMINAL 
BLOCK 2TB 
IN CONTROL BOX
GROUND LUG
Refer to the 
ELECTRICAL DATA 
tables to size the 
power wiring, the  
fuses and the 
disconnect switch.
24 VOLT 
TRANSFORMER
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT
1
 
TERMINALS
CONTROL WIRING
UNIT TERMINAL 
BLOCK 1TB
2
1
24 Volt Thermostat 2TH04701024 or 2TH04701524 
  (with Subbase 2TB04700324). 
2
Terminal strip 1TB - located on relay board in 24-volt section 
   of the unit control box.  
3
Second stage heating is not required on units with a single stage 
  electric heater.
THERMOSTAT
1
 
TERMINALS
UNIT TERMINAL 
BLOCK 1 TB
2
COOLING ONLY (24 VOLT THERMOSTAT)
24 VOLT 
TRANSFORMER
POWER  WIRING
ADD 
JUMPER
ADD 
JUMPER
ADD 
JUMPER