York AY012MA321 User Manual

Page of 16
246814-YTG-D-0606
14
Unitary Products Group
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the 
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO.
AY030MA321
INDOOR COIL MODEL NO.
G2FD036S17
CONDENSER 
ENTERING AIR 
TEMPERATUR
ID CFM
800
1000
1200
ID DB (°F)
80
80
75
80
80
80
80
75
80
80
80
80
75
80
80
ID WB (°F)
57
62
62
67
72
57
62
62
67
72
57
62
62
67
72
65
T.C.
27.2
30.0
29.5
32.7
35.7
28.7
30.4
30.1
33.0
35.7
30.1
30.7
30.6
33.4
35.6
S.C.
25.6
24.4
20.7
20.5
16.4
27.1
26.7
23.0
22.6
17.8
28.6
29.0
25.4
24.7
19.2
KW
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
1.9
2.0
1.9
1.9
1.9
2.0
2.0
75
T.C.
26.6
28.8
28.4
31.4
34.3
28.0
29.2
28.8
31.6
34.3
29.3
29.6
29.3
31.8
34.3
S.C.
25.1
23.7
20.0
20.0
15.9
16.4
25.8
22.1
22.1
17.2
27.8
28.0
24.2
24.1
18.5
KW
2.1
2.1
2.1
2.2
2.2
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.2
2.2
85
T.C.
26.1
27.6
27.2
30.1
32.9
27.2
28.1
27.6
30.2
33.0
28.4
28.5
28.0
30.3
33.0
S.C.
24.5
22.9
19.2
19.5
15.5
25.7
25.0
21.1
21.5
16.6
27.0
27.1
23.0
23.6
17.8
KW
2.3
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
2.4
95
T.C.
25.5
26.4
26.1
28.9
31.5
26.5
26.9
26.4
28.8
31.6
27.5
27.4
26.6
28.7
31.7
S.C.
23.9
22.2
18.5
19.0
15.0
25.0
24.2
20.2
21.0
16.0
26.2
26.1
21.8
23.0
17.1
KW
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.6
2.7
2.6
2.6
2.6
2.6
2.7
105
T.C.
24.6
25.3
25.0
27.5
30.2
25.5
25.8
25.3
27.5
30.2
26.4
26.3
25.5
27.5
30.1
S.C.
23.0
21.8
18.1
18.4
14.6
24.1
23.4
19.8
20.5
15.7
25.1
25.0
21.6
22.6
16.8
KW
2.8
2.8
2.8
2.9
2.9
2.8
2.9
2.8
2.9
2.9
2.9
2.9
2.9
2.9
3.0
115
T.C.
23.7
24.2
24.0
26.3
28.9
24.5
24.7
24.2
26.3
28.8
25.3
25.1
24.4
26.3
28.6
S.C.
22.2
21.4
17.6
17.9
14.3
23.2
22.6
19.5
20.1
15.4
24.1
23.9
21.4
22.2
16.4
KW
3.1
3.1
3.1
3.1
3.2
3.1
3.1
3.1
3.2
3.2
3.2
3.2
3.2
3.2
3.2
125
T.C.
22.8
23.2
23.0
25.0
27.7
23.5
23.6
23.2
25.1
27.4
24.3
23.9
23.4
25.1
27.1
S.C.
21.4
21.0
17.2
17.4
14.0
22.3
21.9
19.2
19.6
15.0
23.1
22.8
21.3
21.8
16.1
KW
3.3
3.3
3.3
3.4
3.5
3.4
3.4
3.4
3.4
3.5
3.4
3.4
3.4
3.4
3.5
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM. 
Air Handler
Coil
T.C. 
S.C. 
KW 
MV12B
FC/MC36B
1.01 1.02 0.97 
MV12B
FC/MC42B
1.02 1.03 0.98 
MV12B
G4FD036H17T2A
1.01 1.02 0.97 
MV12B
G4FD046H17T2A
1.02 1.03 0.98 
MV16C
FC/MC36C
1.02 1.03 0.98 
MV16C
FC/MC42C
1.02 1.03 0.98 
MV16C
G4FD036H21T2A
1.02 1.03 0.98 
MV16C
G4FD042H21T2A
1.02 1.03 0.98 
AHP36
1.00 1.00 1.00 
FC/MC/PC36
1.00 1.00 1.00 
FC/MC/PC42
1.00 1.00 1.00 
G4FA048S17T2A
1.00 1.00 1.00 
G4FD036H17T2A
1.00 1.00 1.00 
G4FD036H21T2A
1.00 1.00 1.00 
G4FD042H21T2A
1.00 1.00 1.00 
G4FD046H17T2A
1.00 1.00 1.00 
HC30
1.00 1.00 1.00 
UC36
1.00 1.00 1.00 
UC42
1.00 1.00 1.00 
Variable Speed Furnace
Coil
T.C.
S.C.
KW
PV8*A12
FC/MC/PC36A
1.01
1.01
1.01
PV8*B16
FC/MC/PC36B
1.02
1.03
0.98
PV8*C16
FC/MC/PC36C
1.0 1.03
0.98
PV8*C20
FC/MC/PC36C
1.02
1.03
0.94
PV9*A12
FC/MC/PC36A
1.01
1.01
1.01
PV9*B12
FC/MC/PC36B
1.01
1.02
1.01
PV9*C16
FC/MC/PC36C
1.01
1.02
0.97
PV9*C20
FC/MC/PC36C
1.01
1.02
0.97
PV8*B16
FC/MC/PC42B
1.02
1.03
0.98
PV8*C16
FC/MC/PC42C
1.02
1.03
0.94
PV8*C20
FC/MC/PC42C
1.02
1.03
0.94
PV9*B12
FC/MC/PC42B
1.01
1.02
0.97
PV9*C16
FC/MC/PC42C
1.01
1.02
0.97
PV9*C20
FC/MC/PC42C
1.01
1.02
0.97
PV8*B16
G4FA048S17T2A
1.02
1.03
0.98
PV9*B12
G4FA048S17T2A
1.01
1.02
0.97
PV8*B16
G4FD036H17T2A
1.0 1.03
0.98
PV9*B12
G4FD036H17T2A
1.01
1.02
1.01
PV8*C16
G4FD036H21T2A
1.02
1.03
0.98
PV8*C20
G4FD036H21T2A
1.02
1.03
0.94
PV9*C16
G4FD036H21T2A
1.01
1.02
0.97
PV9*C20
G4FD036H21T2A
1.01
1.02
0.97
PV8*C16
G4FD042H21T2A
1.02
1.03
0.94
PV8*C20
G4FD042H21T2A
1.02
1.03
0.94
PV9*C16
G4FD042H21T2A
1.01
1.02
0.97
PV9*C20
G4FD042H21T2A
1.01
1.02
0.97
PV8*B16
G4FD046H17T2A
1.02
1.03
0.98
PV9*B12
G4FD046H17T2A
1.02
1.03
0.98
PV8*A12
HC30
1.01
1.01
1.01
PV9*A12
HC30
1.01
1.01
1.01