York DJ 240 User Manual

Page of 40
261660-YTG-D-0708
Johnson Controls Unitary Products
39
ELECTRIC HEATING (DJ***C/E MODELS) 
Nickel chromium electric heating elements shall be provided 
as required by the application with 1 or 2 stage control, as 
required, from 13.5 KW to 72 KW capacities. The heating 
section shall have a primary limit control(s) and automatic 
reset to prevent the heating element system from operating 
at an excessive temperature. Units with Electric Heating shall 
be wired for a single point power supply with branch circuit 
fusing (where required). 
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125° F 
outdoor temperature, exceeding maximum load criteria of 
ARI Standard 340/360. The compressor, with standard 
controls, shall be capable of operation down to 25° F outdoor 
temperature. Accessory low ambient kit shall be available for 
operation to 0° F. Unit shall be provided with fan time delay to 
prevent cold air delivery before heat exchanger warms up 
(Gas heat only). 
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring. 
STANDARD LIMITED WARRANTIES
Compressor 5 Years
Heat Exchanger 10 Years
Electric Heat Element 5 Years
Other Parts 1 Year
OPTIONAL OUTDOOR AIR (Shall be made available by 
either/or): 
ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER
 - Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for 
the outdoor air intake dampers shall not exceed 2% 
when dampers are fully closed and operating against a 
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return 
air damper assembly to take in CFM of outdoor air to 
meet the minimum ventilation requirement of the condi-
tioned space during normal operation. During econo-
mizer operation, a mixed-air temperature control shall 
modulate the outdoor and return air damper assembly to 
prevent the supply air temperature from dropping below 
55°F. Changeover from compressor to economizer oper-
ation shall be provided by an integral electronic enthalpy 
control that feeds input into the basic module. The out-
door intake opening shall be covered with a rain hood 
that matches the exterior of the unit. Water eliminator/fil-
ters shall be provided. Simultaneous economizer/com-
pressor operation is also possible. Dampers shall fully 
close on power loss.
BAS-READY ECONOMIZER - Outdoor and return air 
dampers that are interlocked and positioned by a fully-
modulating, spring return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG.
For units with optional VAV or Simplicity® Intelli-Com-
fort™ control, free-cooling shall be available while the 
outdoor dry bulb temperature (OAT) remains below a 
programmable set-point of the controller. Field-installed 
humidity sensors for either outdoor air or outdoor & 
return air streams are available to provide free-cooling 
based on single-enthalpy or dual-enthalpy configura-
tions, respectively. If free-cooling is available, a call for 
cooling shall modulate the economizer in order to main-
tain a supply air temperature (SAT) programmable set-
point. With the use of a field-installed indoor air quality 
sensor, the controller shall provide Demand Ventilation 
by modulating the economizer dampers to allow more 
outside airflow upon detection of elevated indoor CO
2
 
concentrations above a programmable set-point. With an 
additional field-installed outdoor air quality sensor, Differ-
ential Demand Ventilation shall be provided.
The outdoor intake opening shall be covered with a rain 
hood that matches the exterior of the unit. Water elimina-
tor/filters shall be provided.
Simultaneous economizer/compressor operation is also 
possible. Dampers shall fully close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor and 
return air dampers that are interlocked and positioned by 
a 2-position, spring-return damper actuator. The maxi-
mum leakage rate for the outdoor air intake dampers 
shall not exceed 2% when dampers are fully closed and 
operating against a pressure differential of 0.5 IWG. A 
unit-mounted potentiometer shall be provided to adjust 
the outdoor and return air damper assembly to take in 
the design CFM of outdoor air to meet the ventilation 
requirements of the conditioned space during normal 
operation. Whenever the indoor fan motor is energized, 
the dampers open up to one of two pre-selected posi-
tions - regardless of the outdoor air enthalpy. Dampers 
return to the fully closed position when the indoor fan 
motor is de-energized. Dampers shall fully close on 
power loss. 
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
ROOF CURB - 14" high, full perimeter curb with wood 
nailer (shipped knocked-down). 
100% BAROMETRIC RELIEF DAMPER - Contains a 
rain hood, air inlet screen, exhaust damper and mount-
ing hardware. Used to relieve internal air pressure 
through the unit.