York 120 User Manual

Page of 44
035-17311-002-A-0803
Unitary Products Group
19
TABLE 8:
ELECTRICAL DATA - DM090 (7-1/2 TON) WITHOUT POWER CONVENIENCE OUTLET
TABLE 9:
ELECTRICAL DATA - DM090 (7-1/2 TON) WITH POWER CONVENIENCE OUTLET
FIGURE 19 -  FIELD WIRING DISCONNECT
T E R M I N A L   B L O C K   T B 1
G R O U N D
L U G
T H R E E
P H A S E
P O W E R
S U P P L Y
F A C T O R Y   O R   F I E L D
S U P P L I E D   D I S C O N N E C T
RLA
LRA
FLA
1.5 2
1.52
1.52
1.52
1.52
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
None
--
--
  20.7   21.7   22.9   23.9   25   25
  25
  30
2TP04520950
  5.6
8.5
  20.7   21.7   22.9   23.9   25   25
  25
  30
2TP04521850
  11.3
17.2
  25.3   26.6   28.1   29.3   30   30
  30
  30
2TP04522450
  15
22.8
  32.4   33.6   35.1   36.4   35   35
  40
  40
2TP04523650
 21.3
32.4
 44.3  45.6   47.1   48.3   45
 50
 50
 50
*
Maximum HACR breaker of the same AMP size is applicable.
0.0
Max
Fuse
*
Size
(Amps)
Max Fuse* 
Size
w/Power
Exhaust
3.1
4.1
2.2
Actual
KW
Heater
Amps
Min.
Circuit
Ampacity
(Amps)
380
7.1
54.0
0.8
MCA
w/Power
Exhaust
(Amps)
Pwr
Exh
Motor
Pwr
Conv
Outlet
Electric Heater 
Model No.
FLA
FLA
Voltage
Compressors
OD Fan 
Motors
Supply
Blower
Motor FLA
RLA
LRA
FLA
1.5 2
1.52
1.52
1.52
1.52
ea.
ea.
ea.
HP
HP
HP
HP
HP
HP
HP
HP
HP
HP
None
--
--
  27
  28   29.2   30.2   30   35
  35
  35
2TP04520950
  5.6
8.5
  27
  28   29.2   30.2   30   35
  35
  35
2TP04521850
  11.3
17.2
  33.2   34.5   36   37.2   35   35
  40
  40
2TP04522450
  15
22.8
  40.2   41.5   43   44.2   45   45
  45
  45
2TP04523650
 21.3
32.4
 52.2  53.5   55   56.2   60
 60
 60
 60
*
Electric Heater 
Model No.
Actual
KW
Voltage
Compressors
OD Fan 
Motors
Supply
Blower
Motor FLA
Maximum HACR breaker of the same AMP size is applicable.
Max Fuse* 
Size
w/Power
Exhaust
FLA
FLA
Heater
Amps
Min.
Circuit
Ampacity
(Amps)
MCA
w/Power
Exhaust
(Amps)
Max
Fuse
*
Size
(Amps)
Pwr
Exh
Motor
Pwr
Conv
Outlet
3.1
4.1
2.2
6.3
380
7.1
54.0
0.8