York 36 User Manual

Page of 44
255040-YTG-A-0506
40
Unitary Products Group
internally enhanced copper tubes with all joints 
brazed. Special Phenolic coating shall be available 
as a factory option.
b.
Evaporator and Condenser coils shall be of the 
direct expansion, draw-thru, design.  
Refrigerant Circuit and Refrigerant Safety Components shall 
include:
a.
Independent fixed-orifice expansion devices.
b.
Filter drier/strainer to eliminate any moisture or for-
eign matter.
c.
Accessible service gage connections on both suc-
tion and liquid lines to charge, evacuate, and mea-
sure refrigerant pressure during any necessary 
servicing or troubleshooting without losing charge.
d.
The refrigeration system shall provide at least 15°F 
of sub-cooling at design conditions.
UNIT CONTROLS
a.
Unit shall be complete with self-contained low-volt-
age control circuit protected by a resetable circuit 
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which pro-
vides reset capability at the space thermostat or 
base unit, should any of the following standard 
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil. 
f.
If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor 
over temperature, over current protection.
h.
Unit shall operate with conventional thermostat 
designs and have a low voltage terminal strip for 
easy hook-up.
i.
Unit control board shall have on-board diagnostics 
and fault code display.
j.
Standard controls shall include anti-short cycle and 
low voltage protection, and permit cooling operation 
down to 0°F.
k.
Control board shall monitor each refrigerant safety 
switch independently.
l.
Control board shall retain last 5 fault codes in non 
volatile memory, which will not be lost in the event of 
a power loss.
GAS HEATING SECTION
Shall be designed with induced draft combustion with post 
purge logic, energy saving direct spark ignition, and redun-
dant main gas valve. Venter wheel shall be constructed of 
stainless steel for corrosion resistance. The heat exchanger 
shall be of the tubular type, constructed of T1-40 aluminized 
steel for corrosion resistance and allowing minimum mixed 
air entering temperature of 25°F. Burners shall be of the 
inshot type, constructed of aluminum coated steel and con-
tain air mixture adjustments. All gas piping shall enter the unit 
cabinet at a single location through either the side or curb, 
without any field modifications. Integrated control boards 
shall provide timed control of evaporator fan functioning and 
burner ignition. Heating section shall be provided with the fol-
lowing minimum protection:
a.
Primary and auxiliary high-temperature limit 
switches.
b.
Induced draft motor speed sensor.
c.
Flame roll out switch (manual reset).
d.
Flame proving controls. 
e.
If any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic 
code that indicates which safety switch has tripped.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements, 
shall be provided in a range of 5 thru 30 KW, offering two 
stages of capacity - 16 KW and above on 208/230 volt heat-
ers and 20 KW and above on 460 and 575 volt heaters. The 
heating section shall have a primary limit control(s) and auto-
matic reset to prevent the heating element system from oper-
ating at an excessive temperature. The heating section 
assembly shall slide out of the unit for easy maintenance and 
service. Units with Electric Heating shall be wired for a single 
point power supply with branch circuit fusing (where 
required).
UNIT OPERATING CHARACTERISTICS
a.
Unit shall be capable of starting and running at 
125°F outdoor temperature, exceeding maximum 
load criteria of ARI Standard 210/240.
b.
The compressor, with standard controls, shall be 
capable of operation down to 0°F outdoor tempera-
ture.
c.
Unit shall be provided with fan time delay to prevent 
cold air delivery before heat exchanger warms up 
(Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory 
provided location and be capable of side or bottom entry, to 
minimize roof penetrations and avoid unit field modifications. 
Separate side and bottom openings shall be provided for the 
control wiring.