Units may be moved or lifted with a forklift.  Slotted openings
in the base rails are provided for this purpose.
LENGTH OF FORKS MUST BE A MINIMUM OF 60
INCHES.
 
   
 
  
 
CLEARANCES
All units require particular clearances for proper operation
and service. Installer must make provisions for adequate
ventilation air in accordance with  applicable provisions of the
local building codes. Refer to Table 6 for clearances required
for combustible construction, servicing, and proper unit oper-
ation
.
Before lifting, make sure the unit weight is distrib-
uted equally on the rigging cables so it will lift evenly.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from rig-
ging cable damage with plywood or other suitable
material.
FIGURE 5 -  UNIT 4 POINT LOAD
TABLE 3:
UNIT WEIGHTS
Model
Shipping Weight
*
 (lb.)
*.
Weights include largest gas heat option.
Operating Weight
† 
(lb.)
†.
54kW heater. 
DM090
1056
1051
DM120
1121
1116
DM150
1200
1195
Econ.
85
84
w/ PE
150
148
Elec. Heat
2
49
49
D
A
C
B
L E F T
F R O N T
TABLE 4:
6 POINT LOAD WEIGHT 
Model
Location (lbs.)
*
*.
Weights include largest gas heat option.
A
B
C
D
E
F
DM090
158
142
128
187
207
230
DM120
168
151
136
198
219
244
DM150
180
161
145
212
235
262
TABLE 5:
4 POINT LOAD WEIGHT 
Model
Location (lbs.)
*
*.
Weights include largest gas heat option.
A
B
C
D
DM090
230
197
287
336
DM120
245
209
305
357
DM150
262
224
327
382
FIGURE 6 -  UNIT 6 POINT LOAD
FIGURE 7 -  UNIT CENTER OF GRAVITY
D
A
C
B
E
F
L E F T
F R O N T
FRONT
LEFT
47 1/2"
25 1/2"