InRoom SC 60 Hz User Manual
Installation
Location
Requirements
When deciding where to locate the cooling 
unit, consider cooling needs, air flow, and 
the location of the electrical outlet. The 
cooling unit can be no more than 2.4 m 
(8 ft) from the electrical outlet, condenser 
intake and exhaust access.
Cooling needs. 
Position the cooling unit 
as close as possible to the main heat source 
that requires cooling.
Air flow. 
Position the rear of the cooling 
unit at least 500 mm (20 in) away from a 
wall or other equipment.
Location of electrical outlet. 
Place the 
cooling unit no farther than 2.4 m (8 ft) 
from a dedicated 120V, 60Hz, 15A branch 
circuit receptacle. 
Electrical Hazard: Do not use extension cords with this equipment. Using an extension 
cord reduces circuit protection and will void the warranty. 
Caution: To help avoid loss of cooling, only connect this equipment to a single-outlet 
dedicated circuit.
ON/OF
F
MODE
SLEE
P
FAN
TEMP
TIME
InRoo
m SC
> 500 (20)
> 500 (20)
na3362a
Dimensions are shown in mm (in).