APC ACPA4000 User Manual
7
NetworkAIR ACPA4000
Installation
Where to locate the equipment
When deciding where to locate the
equipment, consider your cooling needs, air
flow, the location of the electrical outlet (no
more than 2.4 m (8 ft) from the equipment),
and access for the condenser intake and
exhaust.
equipment, consider your cooling needs, air
flow, the location of the electrical outlet (no
more than 2.4 m (8 ft) from the equipment),
and access for the condenser intake and
exhaust.
Cooling needs.
Position the equipment as
close as possible to the main source of heat
that requires cooling.
that requires cooling.
Air flow.
Position the equipment so that its
rear is at least 200 mm (8 in) away from a
wall or other equipment.
wall or other equipment.
Location of electrical outlet.
Place the
equipment no farther than 2.4 m (8 ft) from
a dedicated 115V, 60Hz, 20A branch circuit
receptacle.
a dedicated 115V, 60Hz, 20A branch circuit
receptacle.
Electrical Hazard: Do not use extension cords with this equipment. Using an extention
cord reduces circuit protection and voids the warranty.
cord reduces circuit protection and voids the warranty.
Caution: To help avoid loss of cooling, only connect this equipment to a single-outlet
dedicated circuit.
dedicated circuit.
Lock the rolling casters
To prevent the equipment from rolling, press down on the
locking tabs on the two front casters.
locking tabs on the two front casters.
na
014
3a
Dimensions are shown in mm (in).
na
01
7
6a