Operating schedules
Path: Main Menu > Setup > Operating Schedule. 
Program up to eight sets of environmental 
controls that run according to the time and day. 
Scheduling: on/off. 
Select Off to use the default schedule, or On to use the programmed schedules.
Reset schedules. 
Turn all schedules off and reset them to their factory default settings.
Edit schedules. 
Set the cooling options for up to eight time periods.
Note: If schedules overlap, the schedule with the highest day-priority runs. The priority is:
• Highest: SunMonTueWedThuFriSat
• Next Highest: WeekdaysWeekends
• Lowest: Every Day
Schedule: 1 of 8
Select a schedule to modify.
Schedule: On/Off
Activate or deactivate this schedule.
Mode
Choose CoolVent Only, or System Off. See “Mode” on page 20.
Set Point
Set the target temperature for the room. See “Set Point” on 
page 20.
Blower
Set the speed of the blower to High or Low. Use the Low blower 
speed to remove humidity from the room air.
Day
Choose the days for this schedule to run. Options include: Every 
day
WeekdaysWeekendsSunMonTueWedThuFri, and 
Sat.
Start Time
Set the time when this schedule becomes active. Times are entered 
using a 24-hour clock.
Stop Time
Set the time when this schedule becomes inactive. Times are 
entered using a 24-hour clock.