Bryant 569F User Manual

Page of 84
26
ELECTRICAL DATA
569D072-120, 576C120, 569F120 UNITS
LEGEND
*Units are suitable for use on electrical systems where voltage supplied
to the unit terminals is not below or above the listed limits.
NOTES:
1. The MCA and MOCP values are calculated in accordance with the
NEC, Article 440.
2. Motor RLA and LRA values are established in accordance with
Underwriters’ Laboratories (UL), Standard 1995.
3. The 575-v units are UL, Canada-listed only.
4. Convenience outlet is available as either a factory-installed option
or a field-installed accessory and is 115-v, 1 ph, 60 Hz.
UNIT
SIZE
FACTORY-
INSTALLED
OPTION
NOMINAL
VOLTAGE
VOLTAGE
RANGE*
COMPRESSOR
FAN MOTORS
(Qty 2)
POWER
SUPPLY
V-Ph-Hz
MIN
MAX
RLA
LRA
FLA (ea)
LRA (ea)
MCA
MOCP
569D
072
NONE OR DISCONNECT
208/230-3-60
187
254
19.2
146
0.9
1.6
25.8
35
CONVENIENCE OUTLET
30.6
35
NONE OR DISCONNECT
460-3-60
418
506
9.6
73
0.4
0.9
12.8
20
CONVENIENCE OUTLET
15.0
20
NONE OR DISCONNECT
575-3-60
523
632
7.7
58.4
0.4
0.9
10.2
15
CONVENIENCE OUTLET
12.0
15
090
NONE OR DISCONNECT
208/230-3-60
187
254
25.6
190
1.5
3.1
35.0
60
CONVENIENCE OUTLET
39.8
60
NONE OR DISCONNECT
460-3-60
418
506
12.8
95
0.7
1.9
17.4
30
CONVENIENCE OUTLET
19.6
30
NONE OR DISCONNECT
575-3-60
523
632
10.2
76
0.7
1.9
13.8
20
CONVENIENCE OUTLET
15.5
20
120
NONE OR DISCONNECT
208/230-3-60
187
254
37.8
239
1.5
3.1
50.3
60
CONVENIENCE OUTLET
55.1
70
NONE OR DISCONNECT
460-3-60
418
506
17.2
125
0.7
1.9
22.9
30
CONVENIENCE OUTLET
25.1
30
NONE OR DISCONNECT
575-3-60
523
632
13.4
80
0.7
1.9
17.8
25
CONVENIENCE OUTLET
19.5
25
576C
120
NONE OR DISCONNECT
208/230-3-60
187
254
36
198
1.5
3.1
48.0
60
CONVENIENCE OUTLET
52.8
70
NONE OR DISCONNECT
460-3-60
418
506
18
99
0.7
1.9
23.9
35
CONVENIENCE OUTLET
26.1
35
NONE OR DISCONNECT
575-3-60
523
632
14
79
0.7
1.9
18.6
30
CONVENIENCE OUTLET
20.3
30
569F
120
NONE OR DISCONNECT
208/230-3-60
187
254
16
125
1.5
3.1
39.0
50
CONVENIENCE OUTLET
43.8
50
NONE OR DISCONNECT
460-3-60
418
506
8
66.5
0.7
1.9
19.4
25
CONVENIENCE OUTLET
21.6
25
NONE OR DISCONNECT
575-3-60
523
632
6.4
50
0.7
1.9
15.8
20
CONVENIENCE OUTLET
17.5
20
FLA
— Full Load Amps
LRA
— Locked Rotor Amps
MCA
— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection
NEC
— National Electrical Code
RLA
— Rated Load Amps
50
TF
Q00
4
-0
12
5
69D
07
2-
12
0,
 57
6C
12
0,
 5
6
9F
120