GOLD CGi Gas-Fired Water Boiler — Boiler Manual
56
Part Number 550-110-710/0107
Troubleshooting — control module lights 
(cont.)
11c
TURN OFF POWER  to boiler 
at service switch or breaker.
• Remove burner shield (see 
Figure 40, item 4page 60 for
location).
• Verify inlet gas pressure at gas 
valve:
Natural gas — 5.0" w.c. min/14.0" 
w.c. max
Propane — 11.0" w.c. min/14.0" 
w.c. max
Is gas present at gas valve inlet and 
within above range?
CHART 6 — FLAME light flashing and POWER light on steady
ALSO — Troubleshooting failure to establish main flame
Electrical shock hazard — Wherever you see 
TURN OFF POWER , follow the instructions. Failure to follow 
instructions could result in severe personal injury, death or substantial property damage.
No
Yes
• Is pilot flame visible through inspection port?
• Are main manual shutoff valve and boiler gas valve open?
No
Yes
TURN OFF POWER  to boiler at service switch or breaker.
• Open main manual shutoff valve and boiler gas valve (per 
Operating instructions in this manual).
• Turn on power at service switch or breaker. A
Does 
FLAME light flash now?
No
Yes
• Boiler should be in 
normal operating 
sequence.
• Observe operation 
until thermostat is 
satisfied and blower 
has completed its 
post-purge cycle.
• Make sure ground wire 
terminal is securely fastened 
to control module mounting 
screw.
• Check the voltage across 
terminals PV and PV/MV of 
the gas valve.
Is
24 VAC present there?
No
Yes
• Check the voltage across 
terminals MV and PV/MV of 
the gas valve.
Is
24 VAC present there?
No
Yes
No
Yes
• Contact gas supplier to correct 
pressure or gas supply.
• If the wiring from the 
control module to gas 
valve is intact, replace the 
control module.
• Retest.
TURN OFF POWER  to boiler at service switch or breaker.
• Check flame signal — Detach sense lead from ignition control 
(Figure 38, item 8, page 50).
• Connect 
negative lead of MICROAMMETER to control sense 
terminal (Figure 38, item 8, page 50). Connect positive lead of 
MICROAMMETER to sense wire.
• DISCONNECT 
red wire connected to terminal MV of the gas 
valve.
• Turn on power to boiler and allow to cycle. As soon as pilot is 
burning, the MICROAMMETER should read at least 1.0 
microamp.
Is flame signal at least 1.0 microamp?
No
Yes
• If the wiring from the 
control module to gas 
valve is intact, replace the 
control module and retest.
• Verify inlet gas pressure at gas valve:
Natural gas — 5.0" w.c. min/14.0" w.c. max
Propane — 11.0" w.c. min/14.0" w.c. max
Is gas present at gas valve inlet and within above range?
No
Yes
TURN OFF POWER  to 
boiler at service switch or 
breaker.
• Remove burner shield (see 
Figure 40, item 4page 60
for location). 
• Verify pilot gas line is not 
kinked, obstructed or 
damaged and is correctly 
attached to pilot and gas 
valve.
• Verify pilot ignition electrode, 
electrode ceramic and spark 
lead wire from control are in 
good condition. Spark gap 
should be approximately 1/8".
• Correct any above problems, 
replacing pilot if burner or 
wiring is damaged.
• Reinstall burner shield to 
operate boiler for retest after 
any changes or corrections.
• If none of the above corrects 
problem, then replace the 
control module and retest. 
• Verify pilot burner is securely 
attached to pilot bracket, bracket 
is securely attached to cross tie, 
and there is no corrosion on the 
parts which would affect the 
ground path for flame sense.
• Verify that pilot flame rod, flame 
rod ceramic and lead wire from 
control module to flame rod are in 
good condition.
• Correct any above problems, 
replacing pilot if burner or wiring 
is damaged. 
• If none of the previous steps 
(including replacing pilot) 
corrects problem, then replace 
the control module, reinstall 
burner shield and retest.