Crown Boiler KSZ075 User Manual

Page of 36
3
TABLE 1a: GENERAL SPECIFICATIONS
Notes:
1.   Net Ratings are based on piping and pick-up allowances of 1.333.
2.   Burner Capacity Rating, GPH is based on #2 oil  with a Gross Heating
Value equal to 140000 BTU/Gal.
3.   Maximum Working Pressure,  Steam -15 PSI.
4.   Tankless heater ratings based on 40F inlet water, 140F outlet water, and
190F boiler water. Ratings are also based on 5 minute intermittent draws with
10 minutes between draws.
III  Before Installing
1)
Safe, reliable operation of this boiler depends upon installation by a professional heating contractor in strict accordance
with this manual and the requirements of the authority having jurisdiction.
In the absence of an authority having jurisdiction, installation must be in accordance with this manual and the latest
edition of Installation of Oil Burning Equipment (ANSI/NFPA31).
Where required by the authority having jurisdiction, this installation must conform to the latest edition of Standard for
Controls and Safety Devices for Automatically Fired Boilers
 (ANSI/ASME CSD-1).
2)
Make sure that a properly sized chimney is available which is in good condition. Consult the authority having
jurisdiction, Part VI of this manual, and ANSI/NFPA31 for additional information on venting requirements.
Power (“Side Wall”) Venting - Important Note
        Two problems arise when any oil-fired appliance is power vented:
1. There is sometimes an accelerated rate of soot buildup on the oil burner cad-cell, spinner etc.
2. There is a potential for severe damage to the side of the structure in the event that the boiler operates at a high smoke level.
This can happen for many reasons, some of which are out of the control of both the installer and appliance manufacturer.
Crown Boiler Company recommends the use of a chimney to vent the KSZ series boilers.  If a power venter must be used, it is
the responsibility of the installer and power vent manufacturer to “engineer” the power vent system.  CROWN BOILER
COMPANY WILL ASSUME NO RESPONSIBILITY FOR DAMAGE TO SIDING, ETC. FROM A POWER
VENTED OIL-FIRED BOILER.  THIS APPLIES REGARDLESS OF THE CAUSE OF THE SOOTING.
2
MODEL
RATING (gpm)
KSZ065
2.25
KSZ075
2.25
KSZ100
2.50
KSZ090
2.50
KSZ125
2.75
KSZ150
3.00
KSZ120
2.75
KSZ175
3.25
KSZ200
3.50
TABLE 1b: TANKLESS HEATER RATINGS
"A"
"B"
"C"
KSZ065
3
0.6 5
78 000
5600 0
233
1 6 1 /2
8  5 /16
6
KSZ075
3
0.7 5
90 000
6800 0
283
1 6 1 /2
8  5 /16
6
KSZ100
3
1.0 0
11900 0
8900 0
370
1 6 1 /2
8  5 /16
6
KSZ090
4
0.9 0
10800 0
8100 0
338
2 1 1 /2
10  13/16
7
KSZ125
4
1.2 5
14900 0
11 2000
467
2 1 1 /2
10  13/16
7
KSZ150
4
1.5 0
17700 0
13 3000
554
2 1 1 /2
10  13/16
7
KSZ120
5
1.2 0
14400 0
10 8000
450
2 6 1 /2
13  5/16
8
KSZ175
5
1.7 5
20700 0
15 5000
646
2 6 1 /2
13  5/16
8
KSZ200
5
2.0 0
23500 0
17 6000
733
2 6 1 /2
13  5/16
8
Dime nsion s (inches)
Boiler Mo del
Number of 
Se ctions
Bu rner 
In put 
(G al/hr)
DO E Hea ting 
Capacity 
(Btu/hr)
I=B=R Ne t 
Rating (Sq. ft)
I=B=R Net 
Rating (Btu/hr)