BUILDER'S CHOICE SERIES INSTALLATION INSTRUCTIONS
Figure 11 - Termination Cap Locations
DIMENSION  DESCRIPTIONS
A
Clearance above the ground, a veranda, porch, deck or bal-
cony - 12 inches (30 cm) minimum. *
B
Clearance to window or door that may be opened –  10,000
BTUs or less, 6 inches (15 cm) minimum; 10,000-50,000 BTUs,
9 inches (23 cm) minimum; over 50,000 BTUs, 12 inches (30
cm) minimum. *
C
Clearance  to  permanently  closed  window  –  12 inches  (30
cm)  minimum  -  recommended  to  prevent  condensation  on
window.
D
Vertical clearance to ventilated soffit located above the termi-
nation within a horizontal distance of 2 feet (60 cm) from the
centerline of the termination – 18 inches (46 cm) minimum. **
E
Vertical  clearance  to  unventilated  soffit  -  12  inches  (30  cm)
minimum. **
F
Clearance to outside corner - 6 inches (15 cm) minimum.
G
Clearance to inside corner - 6 inches (15 cm) minimum.
H
Not to be installed above a meter/regulator assembly within 3
feet (90 cm) horizontally* from the center line of the regulator
I
Clearance  to  service  regulator  vent  outlet  -  6  feet  (1.8m)
minimum. *
J
Clearance to non-mechanical air supply inlet into building or
the combustion air inlet to any other appliance - 12 inches (30
cm) minimum. *
K
Clearance  to  mechanical  air  supply  inlet  -  6    feet  (1.8  m)
minimum. *
L
Clearance  above  a  paved  sidewalk  or  paved  driveway  lo-
cated on public property - 7 feet (2.1 m) minimum.
A vent may not terminate directly above a sidewalk or paved
driveway  which  is  located  between  two  single  family  dwell-
ings  and  serves  both  dwellings.
M
Clearance under veranda, porch, deck or balcony - 12 inches
(30 cm) minimum. * Recommended 30 inches (76 cm) for vinyl
or  plastic.
Only  permitted  if  veranda,  porch,  deck  or  balcony  is  fully
open on a minimum of 2 sides beneath the floor. *
N
Vertical  clearance  between  two  horizontal  termination  caps
– 12 inches (30 cm) minimum.
O
Horizontal clearance between two horizontal termination caps
– 12 inches (30 cm) minimum.
*
As specified in CGA B149 Installation Codes
Note: Local codes or regulations may require different clear-
ances.
**
Clearance required to vinyl soffit material – 30 inches (76 cm)
minimum. With a vinyl soffit shield – 18 inches (46 cm) mini-
mum.
WARNING!
In  the  U.S.:  Vent  system  termination  is  NOT  permitted  in
screened porches. You must follow side wall, overhang and
ground clearances as stated in the instructions.
In  Canada:  Vent  system  termination  is  NOT  permitted  in
screened  porches.  Vent  system  termination  is  permitted  in
porch areas with two or more sides open. You must follow all
side wall, overhang and ground clearances as stated in the
instructions.
Hearth  &  Home Technologies  assumes  no  responsibility  for
the improper performance of the appliance when the venting
system does not meet these requirements.
Figure 12 - Cap Clearances