DFX & DBX Series Vent Free Fireplaces
FIREPLACE INSTALLATION
NOTICE: A qualified gas appliance installer must connect the heater to the gas supply. 
Consult all local codes.
W
ARNING
Use  new  black  iron  or  steel  pipe.  Internally  tinned  copper  or  copper 
tubing can be used per National Fuel Code, section 2.6.3, providing gas 
meets hydrogen sulfide limits, and where permitted by local codes. Gas 
piping system must be sized to provide minimum inlet pressure (Listed 
on Data Plate) at the maximum flow rate (BTU/hr). Undue pressure loss 
will occur if the pipe is too small.
A manual shutoff valve must be installed upstream of the appliance. 
Union  tee  and  plugged  1/8"  NPT  pressure  tapping  point  should  be 
installed upstream of the appliance. Figure 10
A sediment trap should be installed upstream to prevent moisture and 
contaminants from passing through the pipe to appliance controls and 
burners. Failure to do so could prevent the appliance from operating 
reliable. Figure 11
FP2447
gas connection
3” Min.
To Fireplace
Pipe Coupling
Stainless 
Flexible Tube
Pipe
Locations Pressure Tapping 
Point Installation
Manual Shutoff 
Valve
Gas Supply 
Inlet
FP447
Figure 11 - 
Gas Connection
Tee Joint
Pipe Nipple
Cap
Sediment 
Trap
IMPORTANT:  Loosen  the  pipe  adapter  on  the  flex  tube  before  installing  to  the  system 
piping.
Always use an external regulator for all propane/LPG heaters only, to reduce the supply 
tank pressure to a maximum of 13" w.c. This is in addition to the internal regulator in the 
heater valve.
CHECk GAS TYPE: The gas supply must be the same as stated on the 
heater’s rating plate. If the gas supply is different, DO NOT INSTALL 
THE HEATER. Contact your dealer for the correct model.
W
ARNING