CSDV Series Direct Vent Gas Stove
VENTING INSTALLATION 
INSTALLATION pLANNING 
There are two basic types of direct-vent installation:
• 
Horizontal Termination
•  
Vertical Termination
It is important to select the proper length of vent pipe for the 
type of termination you choose. It is also important to note 
the wall thickness. 
FOR HORIZONTAL TERmINATION
Select the amount of vertical rise desired. The horizontal run 
of venting must have 
1
/
4
" rise for every 12" of run towards the 
termination. 
You  may  use  up  to  three  90°  elbows  in  this  vent  configuration.  Refer  to  Horizontal  Termination 
Configurations
 on Page 16.
FOR VERTICAL TERmINATION
Measure the distance from the stove flue outlet to the ceiling. Add the ceiling thickness, the verti-
cal rise in an attic or second story, and allow for sufficient vent height above the roof line. You may 
use one or two 90° elbows in this vent configuration. Refer to Vertical Termination Configurations 
on Page 18.
NOTE: You may use two 45° elbows in place of a 90° elbow. You must follow rise to run ratios when 
using 45° elbows. The appliance is approved for use with three 90° elbows maximum or a combina-
tion of  90° and 45° elbows up to a maximum of 270°. 
For two-story applications, firestops are required at each floor level. If an offset is needed in the 
attic, additional pipe and elbows will be required.
You may use a chase with a vent termination with exposed pipe on the exterior of the house. Refer 
to Installing Vent System in a Chase below. 
It is very important that the venting system maintain its balance between the combustion air intake and 
the flue gas exhaust. Certain limitations apply to vent configurations and must be strictly followed.
INSTALLING A VENT SySTEm IN AN OUTSIDE CHASE
A chase is a vertical boxlike structure built to enclose venting that runs along the outside of a build-
ing. A chase is required for such venting. 
NOTE: When installing in a chase, you should insulate the chase as you would the outside walls 
of your home. This is especially important in cold climates. Minimum clearance between vent pipes 
and combustible materials such as insulation is 1". 
W
ARNING
Never run the vent pipe level or downward. 
This  may  cause  excessive  temperatures 
which could cause a fire. 
NOTICE
Treatment of firestops and construction of the chase may vary from building 
type to building type. These instructions are not substitutes for the requirements 
of local building codes. you must follow all local building codes.
W
ARNING
Always  maintain  minimum  clearances  around  vent  systems.  The  minimum 
clearances to combustibles for horizontal vent pipe are 2" at the top and 1" 
at the sides and bottom of the vent system. For wall firestops, a 1" minimum 
clearance all around the pipe must be maintained. Do not pack the open air 
spaces with insulation or other materials. This could cause high temperatures 
and may present a fire hazard.