Enviro EF3 User Manual

Page of 43
15
Installation
C
LEARANCES
 
TO
 C
OMBUSTIBLES
 - F
REESTANDING
:
When  installing  this  unit  on  a  combustible  floor  (for  example  linoleum,  hardwood  flooring)  a  non-
combustible hearth pad must be under the unit. The pad must extend at least the width of the appliance 
[22” (558 mm)] and at least the depth of the appliance plus 6” (153 mm) in front of the appliance [29 
3⁄4” (756 mm)].
Side wall to unit   
- 6 inches  (15 cm)
Back wall to unit  
- 1 inches  (2.5 cm)
Corner to unit 
- 1 inches  (2.5 cm)
Door front to edge of floor protection
 
- 6 inches  (15 cm)
30"
(76 cm)
48"
(122 cm)
36"
(91cm)
��
���� ���
��
��� ���
��
��� ���
��
���� ���
���� ����
��
��
��
����
���
���
����� ����������
Figure 10: EF3 Freestanding Clearance to Combustibles. 
Minimum Alcove width    - 36 inches   (91 cm)
Minimum Alcove height  - 48 inches   (122 cm)
Maximum Alcove depth  - 30 inches   (76 cm)
Figure 11: EF3 Freestanding Minimum Alcove Size. 
C
LEARANCES
 
TO
 C
OMBUSTIBLES
 - F
IREPLACE
 I
NSERT
:
10" (25.4 cm) Mantel
8"
(20.3 cm)
8"
(20.3 cm)
S
id
e
W
al
l
Floor Protection; Minimum 6" (15 cm) in front of door
Figure 12: EF3 Fireplace Insert Clearance to Combustibles. 
Refer to Figure 12.
Side wall to unit   
- 8 inches 
(20.3 cm)
Mantel projection  
- 10 inches  (25.4 cm)
Mantel to top of unit  - 8 inches 
(20.3 cm)
Top facing to unit 
- 8 inches 
(20.3 cm)
Side facing to unit 
- 6 inches 
(15.2 cm)
Floor protection 
- 6 inches 
(15.2 cm)
on either side and to the front must be 
protected by non-combustible material.
These dimensions are minimum clearances but it is 
recommended that you ensure sufficient room for 
servicing, routine cleaning and maintenance.