System Sensor 2W-B User Manual

Page of 4
D100-96-00                                                                                               1                                                                                            I56-1800-07R
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
INSTALLATION AND MAINTENANCE INSTRUCTIONS
Photoelectric Smoke Detector
Models:    2W-B, 2WT-B
                4W-B, 4WT-B
Series
Before Installing
Please  read  thoroughly  System  Sensor  manual  A05-1003, 
Applications  Guide  for  System  Smoke  Detectors,  which  provides 
detailed information on detector spacing, placement, zoning, wir-
ing, and special applications. Copies of this manual are available 
from System Sensor at no charge.
NOTICE:  This  manual  shall  be  left  with  the  owner/user  of  this 
equipment.
IMPORTANT: This detector must be tested and maintained regu-
larly  following  NFPA  72  requirements.  At  a  minimum,  cleaning 
should be performed annually.
General Description
Models  2W-B  and  2WT-B  are  2-wire  photoelectric  smoke  detec-
tors;  models  4W-B  and  4WT-B  are  4-wire  photoelectric  smoke 
detectors. All models incorporate a state-of-the-art optical sensing 
chamber  and  an  advanced  microprocessor.  The  microprocessor 
allows  the  detector  to  automatically  adjust  its  sensitivity  back 
to  the  factory  setting  when  it  becomes  more  sensitive  due  to 
contaminants  settling  in  its  chamber.  In  order  for  this  feature 
to  work  properly,  the  chamber  must  never  be  opened  while 
power  is  applied  to  the  smoke  detector.  This  includes  cleaning, 
maintenance or screen replacement. Should it become necessary, 
the  screen/sensing  chamber  is  field  replaceable.  Models  2WT-B 
and  4WT-B  also  feature  a  restorable,  built-in,  fixed  temperature 
(135°F) thermal detector and are also capable of sensing a freeze 
condition if the temperature is below 41°F.
All i
3
 Series detectors are designed to provide open area protec-
tion. Two-wire models must be used with compatible UL Listed 
panels only.
When  used  with  an  i
3
  Series  compatible  control  panel  or  the  i
3
 
Series 2W-MOD module (refer to installation manual D500-46-00), 
the  2W-B  and  2WT-B  are  capable  of  generating  a  “maintenance 
needed”  signal.  The  2W-MOD  can  indicate  a  need  for  cleaning, 
replacement,  or  a  freeze  condition  (2WT-B  only)  at  the  control 
panel or module.
Installation  of  the  2W-B,  2WT-B,  4W-B,  and  4WT-B  detectors  is 
simplified by the use of a mounting base that may be pre-wired 
to  the  system,  allowing  the  detector  to  be  easily  installed  or 
removed. The mounting base installation is further simplified by 
the incorporation of features compatible with drywall fasteners.
Two LEDs on the detector provide a local visual indication of the 
detector’s status: 
Table 1: Detector LED Modes
Green LED
Red LED
Power-up
Blink 10 sec
Blink 10 sec
Normal (standby)
Blink 5 sec
Out of sensitivity
Blink 5 sec
Freeze Trouble
Blink 10 sec
Alarm
Solid
After an initial power-up delay, the red and green LEDs will blink 
synchronously once every ten seconds. It will take approximately 80 
seconds for the detector to finish the power-up cycle (see Table 2).
Table 2: Power-up Sequence for LED Status Indication*
Condition
Duration
Initial LED Status Indication
80 seconds
Initial LED Status Indication
(if excessive electrical noise is present)
4 minutes
*Refer to Electrical Specifications for start-up time in conjunction with panel alarm 
verification.
NOTE:  If,  during  power-up,  the  detector  determines  there  is 
excessive electrical noise in the system such as those caused by 
improper grounding of the system or the conduit, both LEDs will 
blink  for  up  to  4  minutes  before  displaying  detector  status  (see 
Table 2).
After  power-up  has  completed  and  the  detector  is  functioning 
normally within its listed sensitivity range, the green LED blinks 
once every five seconds. If the detector is in need of maintenance 
because its sensitivity has shifted outside the listed limits, the red 
LED blinks once every five seconds. When the detector is in the 
alarm mode, the red LED latches on. The LED indication must not 
be used in lieu of the tests specified under Testing. In a freeze 
trouble condition, the red LED will blink once every 10 seconds 
(refer to Table 1).
To  measure  the  detector’s  sensitivity,  the  i
3
  Series  Model  SENS-
RDR  Infrared  Sensitivity  Reader  tool  (see  Figure  4)  should  be 
used.
Models  2W-B  and  2WT-B  also  include  an  output  that  allows  an 
optional Model RA400Z Remote Annunciator to be connected.