DH100ACDCP Air Duct Smoke Detector
INSTALLATION  AND  MAINTENANCE  INSTRUCTIONS
A Division of Pittway
 3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
Before Installing
Please thoroughly read the System Sensor Guide for Proper 
Use  of  Smoke  Detectors  in  Duct  Applications  
(A05-1004), 
which  provides  detailed  information  on  detector  spacing, 
placement, zoning, wiring, and special applications. Copies 
of  this  manual  are  available  from  System  Sensor.  NFPA 
Standards 72 and 90A should also be referenced for detailed 
information. 
NOTICE: This manual shall be left with the owner/user of 
this equipment.
IMPORTANT: This detector must be tested and maintained 
regularly  following  NFPA  72  requirements.  The  detector 
should be cleaned at least once a year.
Table of Contents                                                 Page
[1] General Description                                                  1
[2] Limitations of Duct Smoke Detectors                          1
[3] Exploded View of Duct Smoke Detector Components  2
[4] Contents of the Duct Smoke Detector Kit                    2
[5] Installation Sequence                                                 2
[6] Duct Smoke Detector Maintenance and Test Procedures 5
[7] Detector Cleaning Procedures                                     7
[8] Board Replacement                                                    8
[9] Specifications                                                            8
Warranty                                                                        8
[1] General Description
An HVAC system supplies conditioned air to virtually every 
area of a building. Smoke introduced into this air duct sys-
tem will be distributed to the entire building. Smoke detec-
tors designed for use in air duct systems are used to sense 
the presence of smoke in the duct. 
Model  DH100ACDCP  Air  Duct  Smoke  Detector  utilizes 
photoelectric  technology  for  the  detection  of  smoke.  This 
detection method, when combined with an efficient hous-
ing design, samples air passing through the duct and allows 
detection of a developing hazardous condition. When suf-
ficient smoke is sensed, an alarm signal is initiated at the 
fire control panel monitoring the detector, and appropriate 
action can be taken to shut off fans, blowers, change over 
air handling systems, etc. These actions can facilitate the 
management of toxic smoke and fire gases throughout the 
areas served by the duct system.
The  DH100ACDCP  detector  is  designed  to  operate  on 
24  VDC/VAC,  120  VAC,  or  240  VAC.  Alarm  and  supervi-
sory relay contacts are available for control panel interface 
(alarm initiation), HVAC control, and other auxiliary func-
tions. Auxiliary relays are also provided for fan shut down 
or signaling of up to 9 other detectors in the loop for mul-
tiple  fan  shut  down.  These  detectors  are  not  designed  for 
2-wire applications.
For testing, the alarm can be enabled by a magnet activated 
test switch or by the optional remote test station. The duct 
smoke  detector  latches  into  alarm  state  when  an  alarm 
occurs. A green LED flashes to indicate power, a red LED 
signals  local  alarm  indication,  and  optional  accessories 
offer a variety of annunciation capabilities.
The  DH100ACDCP  can  be  reset  by  a  momentary  power 
interruption, the reset button on the front cover, the control 
panel, or remote reset accessory. The DH100ACDCP incor-
porates  a  cover  tamper  feature  that  provides  a  trouble 
signal after 7 minutes if the cover is removed or improp-
erly installed.
 Proper installation of the cover removes the 
trouble condition.
[2] Limitations Of Duct Smoke Detectors 
WARNING
The  National  Fire  Protection  Association  has  established 
that  DUCT  DETECTORS  MUST  NOT  BE  USED  AS  A 
SUBSTITUTE FOR OPEN AREA DETECTOR PROTECTION 
as a means of providing life safety. Nor are they a substi-
tute for early warning in a building’s regular fire detection 
system.
System  Sensor  supports  this  position  and  strongly  recom-
mends that the user read NFPA Standards 90A, 72, and 101. 
The DH100ACDCP Air Duct Smoke Detectors are listed per 
UL 268A.
WARNING
This device will not operate without electrical power. Fire 
situations may cause an interruption of power. The system 
safeguards should be discussed with your local fire protec-
tion specialist.
WARNING
This  device  will  not  sense  smoke  unless  the  ventilation 
system is operating and the cover is installed.
WARNING
For this detector to function properly, it MUST be installed 
according to the instructions in this manual. Furthermore, 
the  detector  MUST  be  protected  from  the  elements  and 
operated within ALL electrical and environmental specifi-
cations listed in this manual. Failure to comply with these 
requirements  may  prevent  the  detector  from  activating 
when smoke is present in the air duct.