Emerson Series 3000 MVD User Manual
206
Micro Motion
®
Series 3000 MVD Transmitters and Controllers
Diagnostics and Troubleshooting
22.3
Meter fingerprinting
Note: Meter fingerprinting is available only on systems with the standard core processor.
The meter fingerprinting feature provides snapshots, or “fingerprints,” of twelve process variables, at
four different points of transmitter operation. See Table 22-2.
four different points of transmitter operation. See Table 22-2.
For each process variable, the following values are recorded:
•
For Mech Zero:
-
5-minute running average
-
5-minute running standard deviation
•
For all other process variables:
-
Instantaneous value
-
5-minute running average
-
5-minute running standard deviation
-
Recorded minimum
-
Recorded maximum
To access meter fingerprint data, use the Maintenance menu as shown in Figure 22-1. The transmitter
will report the data in either SI units or English units, as configured from the Units menu item. The
display is updated continuously.
will report the data in either SI units or English units, as configured from the Units menu item. The
display is updated continuously.
Unusually low density reading
Slug flow
Incorrect K2 value
Verify characterization. See
Section 22.16.
Section 22.16.
Sensor erosion
Contact Micro Motion.
Unusually high tube frequency
Sensor erosion
Contact Micro Motion.
Reversed drive coil leads (remote core
processor with remote transmitter
installations)
processor with remote transmitter
installations)
Verify drive coil leads
Unusually low tube frequency
Plugged, partially filled, or coated flow
tube
tube
Check drive gain and tube frequency.
See Section 22.18.
Purge the flow tubes.
See Section 22.18.
Purge the flow tubes.
Unusually low pickoff voltages
Several possible causes
See Section 22.18.5
Unusually high drive gain
Several possible causes
See Section 22.18.3.
Table 22-2
Meter fingerprinting data
Fingerprint time
Description
Process variables recorded
Current
Present-time values
• Mass flow rate
• Volume flow rate
• Density
• Temperature
• Case temperature
• Mech zero
• Volume flow rate
• Density
• Temperature
• Case temperature
• Mech zero
• Tube frequency
• Drive gain
• Left pickoff
• Right pickoff
• Core processor temperature
• Core processor input voltage
• Drive gain
• Left pickoff
• Right pickoff
• Core processor temperature
• Core processor input voltage
Factory
Values at time transmitter left factory
Installation
Values at time of first sensor zero
Last zero
Values at time of most recent sensor
zero
zero
Table 22-1
Process variables problems and possible remedies continued
Symptom
Cause
Possible remedy