Emerson Series 3000 MVD User Manual
Configuration and Use Manual
225
Diagnostics and Troubleshooting
Dia
g
nostics and
T
rou
b
b
lesh
oo
tin
g
tin
g
Sp
eci
ficat
eci
ficat
ion
s
– Mo
del
3350
/3
700
Specific
a
tions
–
Model
330
0
/3
500
Measure
ment P
e
rf
or
mance
mance
3. Poll to make a connection to the core processor.
4. When the core processor is found, click
ProLink > Configuration > Device
and set the
Modbus address to
1
.
5. Click
Apply
.
6. Disconnect ProLink II.
7. Reconnect the RS-485 wiring between the Series 3000 device and the core processor.
To avoid this problem, always power down the transmitter before removing the connector wiring
bracket.
bracket.
Note: Do not confuse the Modbus address of the core processor with the Modbus address of the
transmitter. The Modbus address of the core processor is accessible only when you connect directly to
the core processor.
transmitter. The Modbus address of the core processor is accessible only when you connect directly to
the core processor.
22.10
I/O problems
If you are experiencing problems with I/O, use Table 22-9 to identify an appropriate remedy.
Table 22-9
I/O problems and remedies
Symptom
Possible cause
Possible remedy
No mA output
and
no frequency output
or loop
test failed
Power supply problem
Check power supply and power-supply wiring.
See Section 22.11.
See Section 22.11.
Fault condition present if fault
indicators are set to downscale or
internal zero
indicators are set to downscale or
internal zero
Check the fault indicator settings to verify
whether or not the transmitter is in a fault
condition. See Section 8.4.2 to check the mA
fault indicator or Section 8.5 to check the
frequency fault indicator.
If a fault condition is present, see Section 22.7.
whether or not the transmitter is in a fault
condition. See Section 8.4.2 to check the mA
fault indicator or Section 8.5 to check the
frequency fault indicator.
If a fault condition is present, see Section 22.7.
mA output < 4 mA
Process condition below value
configured for 4 mA
configured for 4 mA
Fault condition if fault indicator is set to
internal zero
internal zero
Check the fault indicator settings to verify
whether or not the transmitter is in a fault
condition. See Section 8.4.2.
If a fault condition is present, check the active
alarm log. See Section 22.6.
whether or not the transmitter is in a fault
condition. See Section 8.4.2.
If a fault condition is present, check the active
alarm log. See Section 22.6.
Open in wiring
Verify all connections.
Bad mA receiving device
Check the mA receiving device or try another
mA receiving device. See Section 22.11.6.
mA receiving device. See Section 22.11.6.
Bad output circuit