232
Micro Motion
®
 Series 3000 MVD Transmitters and Controllers
Diagnostics and Troubleshooting
22.18.5
Low pickoff voltage
Low pickoff voltage can be caused by several problems. See Table 22-13.
22.19
Checking the core processor
Two core processor procedures are available:
You can check the core processor LED. The core processor has an LED that indicates different 
flowmeter conditions. See Table 22-14.
If an A026 alarm is present, you can perform the core processor resistance test to check for a 
damaged core processor.
22.19.1
Checking the core processor LED
To check the core processor LED:
1. Maintain power to the transmitter.
2. Remove the core processor lid. The core processor is instrinsically safe and can be opened in 
all environments. Do not disconnect the 4-wire cable between the core processor and the 
transmitter.
3. Check the core processor LED against the conditions described in Table 22-14 (standard core 
processor) or Table 22-15 (enhanced core processor).
4. To return to normal operation, replace the lid.
Note: When reassembling the meter components, be sure to grease all O-rings.
Table 22-12
Erratic drive gain causes and remedies
Cause
Possible remedy
Wrong K1 characterization constant for sensor
Re-enter the K1 characterization constant. See 
Section 7.3.3.
Polarity of pick-off reversed or polarity of drive reversed
Contact Micro Motion.
Slug flow
Verify flow tubes are completely full of process fluid.
Foreign material caught in flow tubes
Purge flow tubes.
Table 22-13
Low pickoff voltage causes and remedies
Cause
Possible remedy
Faulty wiring runs between the sensor and core processor
Verify wiring. See Section 22.11.2.
Process flow rate beyond the limits of the sensor
Verify that the process flow rate is not out of range of the 
sensor.
Slug flow
Verify flow tubes are completely full of process fluid.
No tube vibration in sensor
Check for plugging.
Verify power to transmitter.
Ensure sensor is free to vibrate (no mechanical binding).
Verify wiring. See Section 22.11.2.
Test coils at sensor. See Section 22.20.
Moisture in the sensor electronics
Eliminate the moisture in the sensor electronics.
The sensor is damaged
Contact Micro Motion.