Emerson Model 1700 User Manual

Page of 350
Configure burst parameters
Display (standard)
Not available
Chinese-language
display
Not available
ProLink II
ProLink
 > Configuration > Device > Burst Setup
ProLink III
Device Tools
 > Configuration > Communications > Communications (HART)
Field Communicator Configure > Manual Setup > Inputs/Outputs > Communications > Set Up Burst Mode
Overview
Burst mode is a mode of communication during which the transmitter regularly
broadcasts HART digital information over the mA output. The burst parameters control
the information that is broadcast when burst mode is enabled.
Tip
In typical installations, burst mode is disabled. Enable burst mode only if another device on the
network requires burst mode communication.
Procedure
1.
Enable Burst Mode.
2.
Set Burst Mode Output as desired.
Label
Description
ProLink II
ProLink III
Field Communi-
cator
Primary Variable
Source (Primary
Variable)
PV
The transmitter sends the primary
variable (PV) in the configured
measurement units in each burst
(e.g., 14.0 g/sec, 13.5 g/sec,
12.0 g/sec).
PV current & % of
range
Primary Variable
(Percent Range/
Current)
% range/current
The transmitter sends the PV’s per-
cent of range and the PV’s actual
mA level in each burst (e.g., 25%,
11.0 mA).
Dynamic vars & PV
current
Process Variables/
Current
Process variables/
current
The transmitter sends PV, SV, TV,
and QV values in measurement
units and the PV’s actual milliamp
reading in each burst (e.g.,
50 g/sec, 23 °C, 50 g/sec,
0.0023 g/cm3, 11.8 mA).
Integrate the meter with the control system
104
 Micro Motion
®
 Model 1700 Transmitters with Analog Outputs