If your transmitter does not have a display, it does not have a status LED. This option is
not available.
To interpret the status LED, see the following table.
Restriction
If LED Blinking is disabled, the status LED will flash only during calibration. It will not flash to indicate
an unacknowledged alarm.
Status LED states
Table 8-1:   
LED behavior
Alarm condition
Description
Solid green
No alarm
Normal operation
Flashing green No active alarm
Previously active alarm has not been acknowl-
edged
Solid yellow
Active low-severity alarm
Alarm has been acknowledged
Flashing yel-
low
Active low-severity alarm
Alarm has not been acknowledged
Solid red
Active high-severity alarm
Alarm has been acknowledged
Flashing red
Active high-severity alarm
Alarm has not been acknowledged
8.4
View and acknowledge status alarms
The transmitter posts status alarms whenever a process variable exceeds its defined limits
or the transmitter detects a fault condition. You can view active alarms, and you can
acknowledge alarms.
8.4.1
View and acknowledge alarms using the display
(standard option)
You can view a list containing all alarms that are active, or inactive but unacknowledged.
From this list, you can acknowledge individual alarms.
Note
Only Fault and Informational alarms are listed. The transmitter automatically filters out alarms with
Status Alarm Severity
 set to Ignore.
Prerequisites
Operator access to the alarm menu must be enabled (default setting). If operator access to
the alarm menu is disabled, you must use another method to view or acknowledge status
alarms.
Transmitter operation
Configuration and Use Manual 
121