Milliamp output problems and recommended actions
 (continued)
Table 10-6:   
Problem
Possible causes
Recommended actions
Consistently incorrect
mA measurement
Loop problem
Output not trimmed correctly
Incorrect flow measurement unit config-
ured
Incorrect process variable configured
LRV and URV are not set correctly
Check the mA output trim. See 
Verify that the measurement units are con-
figured correctly for your application.
Verify the process variable assigned to the
mA output.
Check the settings of Upper Range Value and
Lower Range Value
.
mA output correct at
lower current, but in-
correct at higher cur-
rent
mA loop resistance may be set too high
Verify that the mA output load resistance
is below maximum supported load (see
the installation manual for your transmit-
ter).
10.7
Frequency output problems
Frequency output problems and recommended actions
Table 10-7:   
Problem
Possible causes
Recommended actions
No frequency output
Stopped totalizer
Process condition below cutoff
Fault condition if fault action is set to in-
ternal zero or downscale
Slug flow
Flow in reverse direction from config-
ured flow direction parameter
Bad frequency receiving device
Output level not compatible with receiv-
ing device
Bad output circuit
Incorrect internal/external power con-
figuration
Incorrect pulse width configuration
Output not powered
Wiring problem
Verify that the process conditions are below
the low-flow cutoff. Reconfigure the low-flow
cutoff if necessary.
Check the Fault Action settings. See 
.
Verify that the totalizers are not stopped. A
stopped totalizer will cause the frequency
output to be locked.
Check for slug flow. See 
Check flow direction. See 
.
Verify that the receiving device, and the wir-
ing between the transmitter and the receiv-
ing device.
Verify that the channel is wired and config-
ured as a frequency output.
Verify the power configuration for the fre-
quency output (internal vs. external).
.
.
Consistently incorrect
frequency measure-
ment
Output not scaled correctly
Incorrect flow measurement unit config-
ured
Check the frequency output scaling. See 
.
Verify that the measurement units are con-
figured correctly for your application.
Erratic frequency out-
put
Radio frequency interference (RFI) from
environment
Check for radio frequency interference. See 
.
Troubleshooting
Configuration and Use Manual 