Example: Default display variable configuration
Display variable
Process variable assignment
Display Variable 1
Mass flow
Display Variable 2
Mass total
Display Variable 3
Volume flow
Display Variable 4
Volume total
Display Variable 5
Density
Display Variable 6
Temperature
Display Variable 7
External pressure
Display Variable 8
Mass flow
Display Variable 9
None
Display Variable 10
None
Display Variable 11
None
Display Variable 12
None
Display Variable 13
None
Display Variable 14
None
Display Variable 15
None
Configure Display Variable 1 to track the primary mA output
Display (standard)
OFF-LINE MAINT
> OFF-LINE CONFG > DISPLY > VAR 1
Chinese-language
display
display
Offline Maintain
> Configuration > Display > Configure 1st Var
ProLink II
ProLink
> Configuration > Display > Var1
ProLink III
Device Tools
> Configuration > Transmitter Display > Display Security
Field Communicator Configure > Manual Setup > Display > Display Variables
Overview
You can configure Display Variable 1 to track mA Output Process Variable for the primary mA
output. When tracking is enabled, you can control Display Variable 1 from the display menu.
output. When tracking is enabled, you can control Display Variable 1 from the display menu.
Tip
This feature is the only way to configure a display variable from the display menus (standard display
option only), and it applies only to Display Variable 1.
option only), and it applies only to Display Variable 1.
Procedure
Configure Display Variable 1 to track the primary mA output.
Configure device options and preferences
60
Micro Motion
®
Model 1700 Transmitters with Analog Outputs