Emerson Model 1700 User Manual

Page of 350
CAUTION!
If you set mA Output Fault Action or Frequency Output Fault Action to None, be sure to set Digital
Communications Fault Action
 to None. If you do not, the output will not report actual process data,
and this may result in measurement errors or unintended consequences for your process.
Restriction
If you set Digital Communications Fault Action to NAN, you cannot set mA Output Fault Action or Frequency
Output Fault Action
 to None. If you try to do this, the transmitter will not accept the configuration.
6.3
Configure the frequency output
The frequency output is used to report a process variable. The frequency output
parameters control how the process variable is reported. Your transmitter may have zero
or one frequency output: Channel B can be configured as a frequency output or a discrete
output.
The frequency output parameters include:
Frequency Output Polarity
Frequency Output Scaling Method
Frequency Output Maximum Pulse Width
Frequency Output Fault Action
 and Frequency Output Fault Value
Restriction
The process variable assigned to the primary mA output is automatically assigned to the frequency
output. You cannot assign a different process variable.
Important
Whenever you change a frequency output parameter, verify all other frequency output parameters
before returning the flowmeter to service. In some situations, the transmitter automatically loads a
set of stored values, and these values may not be appropriate for your application.
6.3.1
Configure Frequency Output Polarity
Display (standard)
OFF-LINE MAINT
 > OFF-LINE CONFG > IO > CH B > SET FO > FO POLAR
Chinese-language
display
Offline Maintain
 > Configuration > Input/Output > Channel B Setup > Frequency Output > Polarity
ProLink II
ProLink
 > Configuration > Frequency/Discrete Output > Frequency > Freq Output Polarity
ProLink III
Device Tools
 > Configuration > I/O > Outputs > Frequency Output
Field Communicator Configure > Manual Setup > Inputs/Outputs > Frequency Output > FO Settings > FO Polarity
Integrate the meter with the control system
88
 Micro Motion
®
 Model 1700 Transmitters with Analog Outputs