Emerson Model 1700 User Manual

Page of 350
The default value is 277 milliseconds. You can set Frequency Output Maximum Pulse Width to
0 milliseconds or to a value between 0.5 milliseconds and 277.5 milliseconds. The
transmitter automatically adjusts the value to the nearest valid value.
Tip
Micro Motion recommends leaving Frequency Output Maximum Pulse Width at the default value. Contact
Micro Motion customer service before changing Frequency Output Maximum Pulse Width.
6.3.4
Configure Frequency Output Fault Action and Frequency
Output Fault Level
Display (standard)
Not available
Chinese-language
display
Not available
ProLink II
ProLink
 > Configuration > Frequency/Discrete Output > Frequency > Freq Fault Action
ProLink
 > Configuration > Frequency/Discrete Output > Frequency > Freq Fault Level
ProLink III
Device Tools
 > Configuration > Fault Processing
Field Communicator
Configure
 > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO
Fault Action
Configure
 > Manual Setup > Inputs/Outputs > Frequency Output > FO Fault Parameters > FO
Fault Level
Overview
Frequency Output Fault Action
 controls the behavior of the frequency output if the transmitter
encounters an internal fault condition.
Note
For some faults only: If Last Measured Value Timeout is set to a non-zero value, the transmitter will not
implement the fault action until the timeout has elapsed.
Procedure
1.
Set Frequency Output Fault Action as desired.
The default value is Downscale (0 Hz).
2.
If you set Frequency Output Fault Action to Upscale, set Frequency Fault Level to the desired
value.
The default value is 15000 Hz. The range is 10 to 15000 Hz.
Integrate the meter with the control system
92
 Micro Motion
®
 Model 1700 Transmitters with Analog Outputs