TROUBLESHOOTING
CER-TEMP 80 RECOVERY SYSTEM CHECKOUT PROCEDURE
Use this checkout for Cer-Temp 80 Recovery Systems. (For hot water supply application only)
SYSTEM OPERATION
Checkout Sequence
Contact
Incorrect
Cause
Remedy
Set tank temperature
Circulating pump
Pump and burner
Tank temperature control
Replace.
control (thermostat)
and burner shut
remain on.
(thermostat) defective.
20°F (10°C) below
off.
tank water temperature
With thermal
System wiring is incorrect.
Correct wiring.
balancer, pump off
delay of approx-
Circulating pump
Pump wired for continuous
Correct wiring.
imately 2 minutes.
on.
operation.
Burner on.
Gas valve stuck or defective.
Correct or replace valve.
System wiring is incorrect.
Correct wiring.
Set tank temperature
Circulating pump
Circulating pump
High limit control set too
Replace. (If problem
control (thermostat)
and burner on.
on.
low.
proven to be at this
20°F (10°C) above
control by applying
tank water temperature.
High limit control differential
jumper to terminals.)
too wide.
System wiring is incorrect.
Correct wiring.
Coil protector switch has
Remove control cover,
activated.
depress reset button.
 Gas valve or wiring
Check wiring. Repair or
defective.
replace valve.
Circulating pump
Power off or system
Check power supply
and burner off.
wiring is incorrect.
and  wiring.
Tank temperature control
Replace.
(thermostat) defective.
Burner on.
System wiring is incorrect.
Correct wiring.
Boiler outlet
Circulating pump
Circulating pump
High limit control defective,
Replace.
temperature exceeds
on.
and burner on.
or set too high (max. should
210°F  (100°C).
be set at 200°F).
Set tank temperature
System maintains.
control (thermostat)
desired water
for desired water
temperature.
temperature.
PRE-TROUBLESHOOTING
Before any extensive trouble-shooting, perform the following:
Ensure That:
— Voltage (120 vac) is supplied to the appliance.
— System control (tank temperature control, thermostat, etc.) is calling
for appliance operation (call for heat).
— Other contacts (switches) are closed (relay, low water cutoff, flow
switch, coil protector, pressure switch, etc.).
— Gas supply pressure is within the maximum and minimum operating
ranges listed on the appliance rating plate/label.
— Voltage (24 vac) is supplied by transformer.
— Appliance is wired according to wiring diagram.
Note:  Cross wiring the 24 volt circuit of the relay will short the transformer.
— All wire terminals/connectors are firmly attached to valves, modules,
switches, limit controls, etc.
— For LP models only check for possible lockout condition of the ignition
module.