18
Gas pIpInG
Make sure gas supplied is same type listed on model rating plate. 
The inlet gas pressure must not exceed 14 inch water column (3.5 
kPa)  for  natural  and  propane  gas  (L.P.). The  minimum  inlet  gas 
pressure  shown  on  rating  plate  is  that  which  will  permit  firing  at 
rated input.
All gas piping must comply with local codes and ordinances or with the 
National Fuel Gas Code (ANSI Z223.1/ NFPA-54). Copper or brass 
tubing  and  fittings  (except  tin  lined  copper  tubing)  shall  not  be 
used.
If the gas control valve is subjected to pressures exceeding 1/2 psi 
(3.5 kPa), the damage to the gas control valve could result in a fire 
or explosion from leaking gas.
If the main gas line Shut-off serving all gas appliances is used, also 
turn “off” the gas at each appliance.  Leave all gas appliances shut 
“off” until the water heater installation is complete.
A  gas  line  of  sufficient  size  must  be  run  to  the  water  heater.  
Consult  the  current  edition  of  National  Fuel  Gas  Code  
(ANSI  Z223.1/NFPA  54)  and  your  gas  supplier  concerning  pipe 
size.
There must be:
•  A readily accessible manual shut off valve in the gas supply line 
serving the water heater, and
•  A drip leg (sediment trap) ahead of the gas control valve to help 
prevent dirt and foreign materials from entering the gas control 
valve.
•  A flexible gas connector or a ground joint union between the shut 
off valve and control valve to permit servicing of the unit.
Be  sure  to  check  all  the  gas  piping  for  leaks  before  lighting  the 
water  heater.  Use  a  soapy  water  solution,  not  a  match  or  open 
flame. Rinse off soapy solution and wipe dry.
condensate pIpInG
This water heater is a condensing unit and requires a drain to be 
located in close proximity to allow the condensate to drain safely. 
The condensate drains from the unit at the exhaust tee located at 
the bottom of the unit (see figure 12). Condensate from this water 
heater is mildly acidic. Please note that some local codes require 
that condensate is treated by using a pH neutralizing filter prior to 
disposal.
Caution must be used to ensure that the drain is free and clear of 
debris and will not allow backflow through the condensate hose. 
Consideration must be given to avoid freezing of the condensate 
lines which could  result in excessive build up of condensate inside 
the  water  heater.  Waterproof  heat  tape  may  be  required  to  prevent 
freezing of the condensate lines. Please ensure that the outlet of the 
condensate drain does not create a slippery condition which could 
lead to personal injury.
CONDENSATION  WARNING:  THIS  WATER  HEATER  IS  A 
CONDENSING UNIT AND REQUIRES A DRAIN TO BE LOCATED 
IN  CLOSE  PROXIMITY  TO  ALLOW  CONDENSATE  TO  DRAIN 
SAFELY.  THE  CONDENSATE  DRAINS  FROM  UNIT  AT  THE 
EXHAUST  ELBOW  LOCATED  AT  BOTTOM  OF  UNIT.  NOTE: 
IT  IS  IMPORTANT  THAT  THE  CONDENSATE  HOSE  NOT  BE 
ELEvATED ABOvE  THE  EXHAUST  ELBOW,  SEE  FIGURE  12. 
CONDENSATE BUILD-UP WILL BLOCK THE EXHAUST OUTLET, 
WHICH WILL CAUSE IMPROPER OPERATION.
fIGure 12
the condensate drain line must be routed to a suitable drain. If 
no floor drain is available or the drain is above the level of the 
condensate line, install a condensate pump that is resistant 
to  the  acidic  condensate.  these  pumps  are  available  from 
local distributors. If the pump is not resistant to acidic water, 
a  condensate  neutralizer  must  be  used  ahead  of  the  pump. 
when installing the drain line, note the following:
•  Plastic pipe or tubing must be used to connect the condensate 
drain to a suitable drain or condensate pump. Do not use copper 
tubing, iron, or steel pipe for the condensate drain line.
•  Condensate  drain  lines  should  be  installed  in  conditioned 
areas  only.  Drain  lines  installed  in  areas  that  are  subject  to 
freezing  temperatures  should  be  wrapped  with  a  nationally 
recognized/listed  heat  tape  and/or  approved  insulation  for 
freeze protection. Install per manufacturer’s instructions.
•  Do not common drain with the temperature and pressure relief 
valve or the condensate line from an air conditioner evaporator 
coil.
•  Slope  the  condensate  drain  toward  the  inside  floor  drain  or 
condensate pump.
•  The condensate drain line and connection to the drain piping 
must comply with all local codes.