PVI Industries PV 6323 Leaflet

Page of 2
PV 6323  4/04 
SPECIFICATION FOR DOMESTIC WATER HEATERS 
Condensing , Low NOx, Gas-Fired Water Heaters with Polymer-Lined Storage Tanks 
 
 
 
 
Furnish and install POWER VT condensing gas water heater(s) as manufactured by PVI Industries, LLC  
of Fort Worth, Texas.  Supply in quantities and model numbers as indicated on the plumbing schedule. 
 
 
Emissions 
 
 
NOx emissions will not exceed 30 ppm when corrected to 3% O
2  
 (for inputs greater than 399,000 Btu).  
NOx emissions will not exceed 55 ppm when corrected to 3% O
2
 (for 399,000 Btu input).  These levels will be  
certified by independent agency. 
 
 
Gas and Electrical Consumption 
 
 
The water heater will operate at a minimum of 94% thermal efficiency when tested to ANSI Z21.10.3.   The water 
heater will comply with paragraph 7.2.4.4, the thermal efficiency, the standby loss, and all other requirements of 
ASHRAE 90.1-1999. 
 
 
Pressure Vessel and Heating Surfaces 
 
 
The water heater will be a vertical fire tube design that is constructed and stamped in accordance with Section IV, 
Part HLW of the ASME code.  Both the storage and heating sections of the water heater will be National Board 
Registered for a working pressure of 150 psi and will be pressure tested at 1-1/2 times working pressure.  The fireside of 
the heating surfaces will be of boiler-grade steel.  The waterside of the heating tubes will be sealed in copper.  The 
heating tubes will be rolled, beaded, and seal welded into the tube sheets.  The combustion side of the tube sheet will be 
insulated by a layer of ceramic fiber that will protect the tube sheet from both thermal stresses and failure that can result 
from the accumulation of scale and precipitants. 
 
 
Lining 
 
 The 
lining 
will: 
 
 
be applied only after the tank is completely fabricated and all welding is completed. 
 
 
consist of multiple applications of a high-temperature fluoropolymer.  
 
 
be third-party tested to and comply with NSF 61 standard. 
 
 
 
 
be continuous and nonporous with no interruptions or discontinuities.  
  require 
no sacrificial anode rods for protection. 
 
 
Burner and Venting 
 
 
Combustion will be provided by an induced-draft power burner with a gas train meeting the following agency 
requirement for the input specified: 
 
 
 
___ UL (standard) 
___ FM   
___ IRI   
___ Other ______________________ 
 
 
Water heater will be a category IV, condensing appliance, UL listed for use with CPVC vent or AL 29-4C stainless 
steel vent.  Burner will be configured to accept ____ room air _____ direct inlet combustion air.  Water heater will operate 
with a minimum gas pressure of 4 ½ inches water column. 
 
 
 (continued)